1030002020

Honeywell Valve proving system A4021
Accessoires

Mounting bracket for VQ400 and VE5000 series.



113228/U

Honeywell UV flame sensors C7012A/C/E/F/G
Replacement parts

Ultraviolet sensing tube for C7012 sensor



114465/U

Honeywell UV flame sensors C7061A/F
Accessories

Gasket, silicone rubber. For installing viewing window or lens(3pcs required)



117053/U

Honeywell Burner Controls DBC2000-series
Accessories for use with DBC2000 (see dedicated chapter for details)

Cable (ca. 250mm) with jack plug for remote 0..15 micro-ampere flame signal reading. For use with jack plug socket on the front of DBC2000 and R4343 or on plug-in amplifier of R4348.



118367A/U

Honeywell UV flame sensors C7012A/C/E/F/G
Accessories

Swivel mount for adjustable positioning of the UV sensor



124198/U

Honeywell UV flame sensors C7012A/C/E/F/G
Accessories

Mounting flange with 1" NPT internal thread for mounting on 1" sight pipe (to replace standard 3/4" NPT flange), for C7012A/E/G only



124204/U

Honeywell UV flame sensors C7012A/C/E/F/G
Accessories

Quartz focussing lens



129464M/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")
Replacement tube for C7035

Ultraviolet sensing tube (-18o to 121oC) for C7035/C7061 flame scanners



129464N/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")
Replacement tube for C7035

Ultraviolet sensing tube (-40o to 121oC) for C7035/C7061 flame scanners



133568/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
Accessories for V4055 actuators

Auxiliary Switch Bag Assembly (not for models with maximum flow limit switch).



133569/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
Accessories for V4055 actuators

Valve-Closed Indication Switch Bag Assembly



14026/U

Honeywell Pressuretrol Controllers


Steam Trap Black Iron Siphon Loop for L404 or L91



190971B/U

Honeywell UV flame sensors C7012A/C/E/F/G
Replacement parts

Coil and shutter assembly for C7012E/F models only



190971E/U

Honeywell UV flame sensors C7076
Replacement shutter assembly for C7076

Replacement shutter and coil assembly for C7076, with black painted shutter



191002B/U

Honeywell UV flame sensors C7076
Replacement internal chassis for C7076

Replacement electronic chassis module, excluding sensing tube for C7076A/D models (120Vac)



191002D/U

Honeywell UV flame sensors C7076
Replacement internal chassis for C7076

Replacement electronic chassis module, excluding sensing tube for C7076A/D models (230Vac)



191053/U

Honeywell UV flame sensors C7076
Replacement tube for C7076

Ultraviolet sensing tube for C7076 sensor



203541/U

Honeywell Burner Controls EC/RM7800-series
Parts

5-wire connector for S7800/10/20



203765/U

Honeywell Burner Controls EC/RM7800-series
Parts

Remote mounting bracket for S7800



221818A/U

Honeywell Burner Controls EC/RM7800-series
Parts

Display extension cable assembly. Cable length 1.5 m



221818C/U

Honeywell Burner Controls EC/RM7800-series
Parts

Display extension cable assembly. Cable length ca. 3 m. Note: assure no electrical noise is present to avoid connection problems, due to extra long cable.



32002935-001/U

Honeywell ControLinks - Electronic Fuel-Air Ratio Control System
Accessories for ML7999 actuators

Weather proofing kit (NEMA 3 - IP54) for ML7999



32004925-001

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1
Accessories

Closed Position Indicator switch



32008001-002/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Accessories
Product description: SLATE Connector Kit
Comment: Included with modules


45.002.208-001B

Honeywell Pressure switch for general gas- and air application C6045D


Mounting bracket with screws (20sets per carton)



50023821-001/U

Honeywell Burner Controls EC/RM7800-series
Parts

Nema 4 cover assembly for remote mounting of S7800 display.



50023821-002/U

Honeywell Burner Controls EC/RM7800-series
Parts

Nema 4 cover assembly for remote mounting of S7800 display. Incl. remote reset button and wiring.



50096820-001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Accessories
Product description: SLATE Extension Cable


50123928-001

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Accessories
Product description: R8001M Low Torque Actuator Mounting Kit for use with Maxon CV Series Valves


600U

Honeywell Signal processors, single channel

Single channel input for S700/S800 viewing heads. And one model for flame detection with a flame rod.
Temperature range: 0...50C
Hardware outputs: Flame relay: 2 x SPDT
Self-check relay: 1 x SPDT
0..20 mA or 4..20 mA (selectable)

Model for flame detection by flame rod.
Product description: Flame monitoring system for use with a flame rod.
Supply voltage: 85..264 Vac


700-1

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Swivel mount for S700/S800. 1" x 1/2" NPT



700-2

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Swivel mount for S700/S800. Flanged x 1/2" NPT



700-3

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Swivel mount for S700/S800. 1/2" x 1/2" NPT



700ACC

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

S700 cooling jacket for Vortex cooler



700ACSP

Honeywell Signal processors, single channel

Single channel input for S700/S800 viewing heads. And one model for flame detection with a flame rod.
Temperature range: 0...50C
Hardware outputs: Flame relay: 2 x SPDT
Self-check relay: 1 x SPDT
0..20 mA or 4..20 mA (selectable)

Standard models, 700xxSP series
Product description: Adjustable sensitivity signal processor for S700/S800
Supply voltage: 85..264 Vac


700CRLT

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Liquid tight cable restaint for S700/S800



700DA

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Delrin adapter replacement for S700. 1/2" NPT model



700DCSP

Honeywell Signal processors, single channel

Single channel input for S700/S800 viewing heads. And one model for flame detection with a flame rod.
Temperature range: 0...50C
Hardware outputs: Flame relay: 2 x SPDT
Self-check relay: 1 x SPDT
0..20 mA or 4..20 mA (selectable)

Standard models, 700xxSP series
Product description: Adjustable sensitivity signal processor for S700/S800
Supply voltage: 24 Vdc


700LTA

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Liquid tight cable adapter for S700/S800. 3/8" NPT model



700RAA

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Right angle adapter for S700/S800. 1/2" x 1/2" M/F



700UA

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Ultem heat insulating nipple for S700. 1/2" (view) - 1/4" air purge.



7616BR/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
Accessories for V4055 actuators

Damper Crank Arm (damper arm and clip)



800DA

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Delrin adapter replacement for S800. 1/2" model.



800UA

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

Ultem heat insulating nipple for S800. 1/2" (view) - 1/4" air purge.



A4021A1002

Honeywell Valve proving system A4021

The A4021 is a self-checking microprocessor based Valve Proving System (VPS). The A4021 checks the effective closure of automatic shut-off valves by measuring the differential pressure between two valves during the test sequence.
The A4021 is specially designed to be used as proving system to check the effective closure of the valves before burner start up (pre-configuration) or at the end of a heat demand (post-configuration).
Approvals: CE approved (50Hz) according EN1643:2000 (spare part ONLY for non-MD applications installed before 2017)
Protection class: IP40, only with subbase ZL030001
Ambient temperature: -10...60C
Maximum humidity: 95%rh
Remote reset.
Alarm output potential free NO contact.
Uses the NO contact of a standard gas pressure switch, that is set to 1/2x the nominal inlet pressure.
Suggested gas pressure switches: C6097 series C60VR40xxx series DG series
Note: To be used in Europe only as spare part. For new installations the Kromschroeder TC 2 or TC 3 can be used. For details visit http://www.docuthek.com (copy/paste link into web browser)
Outputs: 1xSPST
Operation: Automatic
Runtime: 60s
Comment: Test time per valve 25sec.


A4021A1010

Honeywell Valve proving system A4021

The A4021 is a self-checking microprocessor based Valve Proving System (VPS). The A4021 checks the effective closure of automatic shut-off valves by measuring the differential pressure between two valves during the test sequence.
The A4021 is specially designed to be used as proving system to check the effective closure of the valves before burner start up (pre-configuration) or at the end of a heat demand (post-configuration).
Approvals: CE approved (50Hz) according EN1643:2000 (spare part ONLY for non-MD applications installed before 2017)
Protection class: IP40, only with subbase ZL030001
Ambient temperature: -10...60C
Maximum humidity: 95%rh
Remote reset.
Alarm output potential free NO contact.
Uses the NO contact of a standard gas pressure switch, that is set to 1/2x the nominal inlet pressure.
Suggested gas pressure switches: C6097 series C60VR40xxx series DG series
Note: To be used in Europe only as spare part. For new installations the Kromschroeder TC 2 or TC 3 can be used. For details visit http://www.docuthek.com (copy/paste link into web browser)
Outputs: 1xSPST
Operation: Automatic
Runtime: 60s
Comment: Test time per valve 25sec.


ACC55XBE

Honeywell Industrial flame monitoring - Viewing Heads
Parts and accessories: Mounting

Air cooling canister for S550xBE viewing heads. 1/4 inch air inlet port. Use with vortex coolers. Not for older S5xx and S550BE-EX models.



ASY785

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Electrical

Connector cable with LED and 50-ft (15 m)C330S cable with braided shield for S700/S800.



ASY785-200

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Electrical

Connector cable with LED and 200-ft (60 m)cable with braided shield for S700/S800.



ASYS55XBE

Honeywell Industrial flame monitoring - Viewing Heads
Parts and accessories: Electrical

C330S cable with connector for S55xBE series viewing heads, length 50 Ft / 15 m



ASYS55XBE-200

Honeywell Industrial flame monitoring - Viewing Heads
Parts and accessories: Electrical

C330S cable with connector for S55xBE series viewing heads, length 200 Ft / 60 m



ASYU2S

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - 12 conductor C22S ITC/CIC approved cable for U2-S, with factory mounted R-518-10 connector

Cable length 50 Ft (15m )



ASYU2S-100

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - 12 conductor C22S ITC/CIC approved cable for U2-S, with factory mounted R-518-10 connector

Cable length 100 Ft (30 m)



ASYU2S-200

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - 12 conductor C22S ITC/CIC approved cable for U2-S, with factory mounted R-518-10 connector

Cable length 200 Ft (60 m)



ASYU2S-300

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - 12 conductor C22S ITC/CIC approved cable for U2-S, with factory mounted R-518-10 connector

Cable length 50 Ft (90 m)



Approval

Honeywell Intelligent safety combination shutoff gas valve with integrated smart technology

The "Vulcan" SV2 Series servo regulated combination valves are used for control and regulation of gaseous fuels in gas fired power burners, atmospheric gas boilers, melting furnaces, incinerators and other gas consuming appliances. These smart combination valves are available in various configurations from 3/4" up to 3". the following different versions:
Designed for but not limited to commercial burner and boiler applications
Gas valve type: Class A safety shut-off valves
Port connection: flanges
Media: Natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE, UL, CSA
Note: Contact a Honeywell Thermal Solutions Representative for more information.
Supply voltage: 24/120/230 Vac

Downloads
Comment: GAR CE certificate


BC1000A0110F

Honeywell Flame relays BC1000

The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals: CE approved against EN298:2003 for intermittent operation, use as spare part only for non-MD installations before 2015, AGA
Protection class: IP00
Ambient temperature: -20...60C
Maximum humidity: 90%rh
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: Spare part only for commercial burner applications.

115Vac versions
Outputs: 1xSPST
Operation: Manual stop/start
Flame failure response time: 2s
Flame detector: Rectification
Supply voltage: 110..120 Vac
Comment: Flame rod (or C7012A/G)


BC1000A0110U

Honeywell Flame relays BC1000

The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals: CE approved against EN298:2003 for intermittent operation, use as spare part only for non-MD installations before 2015, AGA
Protection class: IP00
Ambient temperature: -20...60C
Maximum humidity: 90%rh
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: Spare part only for commercial burner applications.

115Vac versions
Outputs: 1xSPST
Operation: Manual stop/start
Flame failure response time: 2s
Flame detector: UV
Supply voltage: 110..120 Vac
Comment: C7027, C7035, C7044


BC1000A0220F

Honeywell Flame relays BC1000

The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals: CE approved against EN298:2003 for intermittent operation, use as spare part only for non-MD installations before 2015, AGA
Protection class: IP00
Ambient temperature: -20...60C
Maximum humidity: 90%rh
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: Spare part only for commercial burner applications.

230Vac versions
Outputs: 1xSPST
Operation: Manual stop/start
Flame failure response time: 2s
Flame detector: Rectification
Supply voltage: 220..240 Vac
Comment: Flame rod (or C7012A/G)


BC1000A0220U

Honeywell Flame relays BC1000

The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals: CE approved against EN298:2003 for intermittent operation, use as spare part only for non-MD installations before 2015, AGA
Protection class: IP00
Ambient temperature: -20...60C
Maximum humidity: 90%rh
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: Spare part only for commercial burner applications.

230Vac versions
Outputs: 1xSPST
Operation: Manual stop/start
Flame failure response time: 2s
Flame detector: UV
Supply voltage: 220..240 Vac
Comment: C7027, C7035, C7044


BC1000B1000

Honeywell Flame relays BC1000

The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals: CE approved against EN298:2003 for intermittent operation, use as spare part only for non-MD installations before 2015, AGA
Protection class: IP00
Ambient temperature: -20...60C
Maximum humidity: 90%rh
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: Spare part only for commercial burner applications.

115Vac versions
Outputs: 1xSPDT
Operation: Flame switch
Flame failure response time: <1s
Flame detector: Rectification
Supply voltage: 110..120 Vac
Comment: Flame rod (or C7012A/G)


BC1000B1018

Honeywell Flame relays BC1000

The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals: CE approved against EN298:2003 for intermittent operation, use as spare part only for non-MD installations before 2015, AGA
Protection class: IP00
Ambient temperature: -20...60C
Maximum humidity: 90%rh
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: Spare part only for commercial burner applications.

230Vac versions
Outputs: 1xSPDT
Operation: Flame switch
Flame failure response time: <1s
Flame detector: Rectification
Supply voltage: 220..240 Vac
Comment: Flame rod (or C7012A/G)


BC1000B2001

Honeywell Flame relays BC1000

The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals: CE approved against EN298:2003 for intermittent operation, use as spare part only for non-MD installations before 2015, AGA
Protection class: IP00
Ambient temperature: -20...60C
Maximum humidity: 90%rh
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: Spare part only for commercial burner applications.

115Vac versions
Outputs: 1xSPDT
Operation: Flame switch
Flame failure response time: <1s
Flame detector: UV
Supply voltage: 110..120 Vac
Comment: C7027, C7035, C7044


BC1000B2019

Honeywell Flame relays BC1000

The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals: CE approved against EN298:2003 for intermittent operation, use as spare part only for non-MD installations before 2015, AGA
Protection class: IP00
Ambient temperature: -20...60C
Maximum humidity: 90%rh
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: Spare part only for commercial burner applications.

230Vac versions
Outputs: 1xSPDT
Operation: Flame switch
Flame failure response time: <1s
Flame detector: UV
Supply voltage: 220..240 Vac
Comment: C7027, C7035, C7044


Brochure

Honeywell Intelligent safety combination shutoff gas valve with integrated smart technology

The "Vulcan" SV2 Series servo regulated combination valves are used for control and regulation of gaseous fuels in gas fired power burners, atmospheric gas boilers, melting furnaces, incinerators and other gas consuming appliances. These smart combination valves are available in various configurations from 3/4" up to 3". the following different versions:
Designed for but not limited to commercial burner and boiler applications
Gas valve type: Class A safety shut-off valves
Port connection: flanges
Media: Natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE, UL, CSA
Note: Contact a Honeywell Thermal Solutions Representative for more information.
Supply voltage: 24/120/230 Vac

Downloads
Comment: Brochure


C22S

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - 12 conductor C22S ITC/CIC approved cable for U2-S, with factory mounted R-518-10 connector

12 Conductor cable with braided shield. Orderable in 1 Ft (30.48 cm) incrementals, minimum length is 15 Ft.



C330S

Honeywell Industrial flame monitoring - Viewing Heads
Parts and accessories: Electrical

4 Conductor cable with braided shield, excl. connector. Orderable in 1 Ft (30.48 cm) incrementals, minimum length is 15 Ft.



C6045D1019

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Direct mount on G1/4" connection
Pressure adjustment range: 5...50mbar
Max. pressure: 200mbar


C6045D1027

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Direct mount on G1/4" connection
Pressure adjustment range: 15...150mbar
Max. pressure: 300mbar


C6045D1043

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Direct mount on G1/4" connection
Pressure adjustment range: 0.2...3mbar
Max. pressure: 100mbar


C6045D1050

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Direct mount on G1/4" connection
Pressure adjustment range: 1...10mbar
Max. pressure: 100mbar


C6045D1068

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Including mounting bracket with screws
Pressure adjustment range: 0.2...3mbar
Max. pressure: 100mbar


C6045D1076

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Including mounting bracket with screws
Pressure adjustment range: 5...50mbar
Max. pressure: 200mbar


C6045D1084

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Including mounting bracket with screws
Pressure adjustment range: 15...150mbar
Max. pressure: 300mbar


C6045D1092

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Including mounting bracket with screws
Pressure adjustment range: 1...10mbar
Max. pressure: 100mbar


C6045D1100

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Including mounting bracket with screws and 2m (L) x 4mm (ID) tubing and nipples for air duct applications
Pressure adjustment range: 1...10mbar
Max. pressure: 100mbar


C6045D1118

Honeywell Pressure switch for general gas- and air application C6045D

For monitoring pressure of air and non-aggressive (fuel)gases.
Kind of pressure: differential pressure, relative
Pressure connection: positive pressure: G1/4"
negative pressure: G1/8"
Electrical connection: PG13,5
Protection class: IP40
Housing material: aluminium die casting
Media temp.: -15...70C
Ambient temperature: -15...70C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 2 A (inductive); 10 A resistive
Approvals: CE approved against EN1854:2010 (GAR)
Mounting position: horizontal or vertical
Large membrane for maximum accuracy

Including mounting bracket with screws and 2m (L) x 4mm (ID) tubing and nipples for air duct applications
Pressure adjustment range: 0.2...3mbar
Max. pressure: 100mbar


C6097A1004/U

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

American models for pipe mount, G1/4" connection. Auto recycle. Break on pressure fall.
Pressure adjustment range: 1...12.5mbar
Differential pressure setpoint range: 6...10.5mbar
Max. pressure: 300mbar


C6097A1012/U

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

American models for pipe mount, G1/4" connection. Manual reset. Break on pressure fall.
Pressure adjustment range: 7...52mbar
Differential pressure setpoint range: 6...10.5mbar
Max. pressure: 500mbar


C6097A1053/U

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

American models for pipe mount, G1/4" connection. Auto recycle. Break on pressure fall.
Pressure adjustment range: 7...52mbar
Differential pressure setpoint range: 0.6...1.2mbar
Max. pressure: 600mbar


C6097A1061/U

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

American models for flange mount. Manual reset. Break on pressure fall.
Pressure adjustment range: 7...52mbar
Differential pressure setpoint range: 0.6...1.2mbar
Max. pressure: 600mbar


C6097A1079/U

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

American models for pipe mount, G1/4" connection. Auto recycle. Break on pressure fall.
Pressure adjustment range: 30...150mbar
Differential pressure setpoint range: 2.7...6mbar
Max. pressure: 600mbar


C6097A2110

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

European models for pipe mount, G1/4" connection. Uses PG11 cable gland.
Pressure adjustment range: 1...10mbar
Differential pressure setpoint range: ...0.4mbar
Max. pressure: 200mbar


C6097A2200

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

European models for flange mount on valve body. Uses DIN connector (not included).
Pressure adjustment range: 2.5...50mbar
Differential pressure setpoint range: ...0.6mbar
Max. pressure: 300mbar


C6097A2210

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

European models for pipe mount, G1/4" connection. Uses PG11 cable gland.
Pressure adjustment range: 2.5...50mbar
Differential pressure setpoint range: ...0.6mbar
Max. pressure: 300mbar


C6097A2300

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

European models for flange mount on valve body. Uses DIN connector (not included).
Pressure adjustment range: 30...150mbar
Differential pressure setpoint range: ...2.8mbar
Max. pressure: 500mbar


C6097A2310

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

European models for pipe mount, G1/4" connection. Uses PG11 cable gland.
Pressure adjustment range: 30...150mbar
Differential pressure setpoint range: ...2.8mbar
Max. pressure: 500mbar


C6097A2400

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

European models for flange mount on valve body. Uses DIN connector (not included).
Pressure adjustment range: 100...500mbar
Differential pressure setpoint range: ...7mbar
Max. pressure: 600mbar


C6097A2410

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

European models for pipe mount, G1/4" connection. Uses PG11 cable gland.
Pressure adjustment range: 100...500mbar
Differential pressure setpoint range: ...7mbar
Max. pressure: 600mbar


C6097B1002/U

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

American models for pipe mount, G1/4" connection. Manual reset. Break on pressure rise.
Pressure adjustment range: 30...150mbar
Differential pressure setpoint range: 25...30mbar
Max. pressure: 600mbar


C6097B1101/U

Honeywell Pressure switch for general gas- and air application C6097

The C6097 Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes.
Kind of pressure: differential pressure, relative
Pressure connection: Two models are available: pipe mount or flange mount on valve body.
Pipe mount models: positive pressure: G1/4"
Pipe mount models: negative pressure: G1/8"
Flange mount models: direct mount on valve body
Electrical connection: PG11 or DIN plug
Protection class: IP54
Housing material: Bottom part: aluminium die cast
Case: blue coloured polybutylene terephthalate
Cover: transparent polycarbonate
Media temp.: -15...80C
Ambient temperature: -15...60C
Switch function/capacity: Switch action: SPDT
Max voltage: 250Vac
Min voltage: 24Vac
Max resistive load: 5 A
Max inductive load (pf=0.6): 3 A
Min load: 50 mA
Approvals: C6097A1/B1 models: UL (US+C), CSA (US+C), FM
C6097A2 models: CE EN1854:2010 (GAR)
Mounting position: horizontal or vertical
C6097A1 models are calibrated for pressure fall (approved for use as minimum pressure limiter in NA) and have psi or in.wc scale
C6097B1 models are calibrated for pressure rise (approved for use as maximum pressure limiter in NA) and have psi or in.wc scale
C6097A2 models are calibrated for nominal pressure (CE approved for use as minimum or maximum pressure limiter in EU) and have mbar scale

American models for pipe mount, G1/4" connection. Auto recycle. Break on pressure rise.
Pressure adjustment range: 103...480mbar
Differential pressure setpoint range: 7...21mbar
Max. pressure: 600mbar


C60VR40017

Honeywell Pressure switch for gas application C60VR

Compact gas pressure switch based on the Kromschroeder DG.C series for mounting on the side position of VQ400 dual valves and VRB00/VR400/V4730 combination gas valves.
The C60VR40xxx has an adjustable setpoint and performs minimum gas pressure supervision in a safe start interlock circuit.
The C60VR40xxx is designed to be fitted directly on the valve body of the applicable gas valve body, using two mounting screws and an O-ring.
Kind of pressure: overpressure, relative
Pressure connection: Flanged, directly on valve body.
Electrical connection: DIN plug
Protection class: IP00 (IP54 with DIN plug mounted)
Housing material: Body: aluminium
Cover: reinforced PBT glassfibre
Ambient temperature: -15...60C
End switch function/capacity: Switch action: 1x SPDT
Resistive: 5A
Inductive (COS PHI = 0.6): 0.5A
Contact Resistance (initial): < 80 mOhm
Approvals: C60VR40 models: CE (EN 1854)
C60VRT40 models: UL
Mounting position: horizontal
DIN plug not included.
Maximum test pressure 2 Bar < 15 minutes.

Models for Europe
Pressure adjustment range: 2...17mbar
Differential pressure: 1.5...2.5mbar
Max. pressure: 100mbar


C60VR40040

Honeywell Pressure switch for gas application C60VR

Compact gas pressure switch based on the Kromschroeder DG.C series for mounting on the side position of VQ400 dual valves and VRB00/VR400/V4730 combination gas valves.
The C60VR40xxx has an adjustable setpoint and performs minimum gas pressure supervision in a safe start interlock circuit.
The C60VR40xxx is designed to be fitted directly on the valve body of the applicable gas valve body, using two mounting screws and an O-ring.
Kind of pressure: overpressure, relative
Pressure connection: Flanged, directly on valve body.
Electrical connection: DIN plug
Protection class: IP00 (IP54 with DIN plug mounted)
Housing material: Body: aluminium
Cover: reinforced PBT glassfibre
Ambient temperature: -15...60C
End switch function/capacity: Switch action: 1x SPDT
Resistive: 5A
Inductive (COS PHI = 0.6): 0.5A
Contact Resistance (initial): < 80 mOhm
Approvals: C60VR40 models: CE (EN 1854)
C60VRT40 models: UL
Mounting position: horizontal
DIN plug not included.
Maximum test pressure 2 Bar < 15 minutes.

Models for Europe
Pressure adjustment range: 5...40mbar
Differential pressure: 1.5...2.5mbar
Max. pressure: 100mbar


C60VR40040G

Honeywell Pressure switch for gas application C60VR

Compact gas pressure switch based on the Kromschroeder DG.C series for mounting on the side position of VQ400 dual valves and VRB00/VR400/V4730 combination gas valves.
The C60VR40xxx has an adjustable setpoint and performs minimum gas pressure supervision in a safe start interlock circuit.
The C60VR40xxx is designed to be fitted directly on the valve body of the applicable gas valve body, using two mounting screws and an O-ring.
Kind of pressure: overpressure, relative
Pressure connection: Flanged, directly on valve body.
Electrical connection: DIN plug
Protection class: IP00 (IP54 with DIN plug mounted)
Housing material: Body: aluminium
Cover: reinforced PBT glassfibre
Ambient temperature: -15...60C
End switch function/capacity: Switch action: 1x SPDT
Resistive: 5A
Inductive (COS PHI = 0.6): 0.5A
Contact Resistance (initial): < 80 mOhm
Approvals: C60VR40 models: CE (EN 1854)
C60VRT40 models: UL
Mounting position: horizontal
DIN plug not included.
Maximum test pressure 2 Bar < 15 minutes.

Models for Europe
Pressure adjustment range: 5...40mbar
Differential pressure: 1.5...2.5mbar
Max. pressure: 100mbar
Comment: Gold plated contacts


C60VR40110

Honeywell Pressure switch for gas application C60VR

Compact gas pressure switch based on the Kromschroeder DG.C series for mounting on the side position of VQ400 dual valves and VRB00/VR400/V4730 combination gas valves.
The C60VR40xxx has an adjustable setpoint and performs minimum gas pressure supervision in a safe start interlock circuit.
The C60VR40xxx is designed to be fitted directly on the valve body of the applicable gas valve body, using two mounting screws and an O-ring.
Kind of pressure: overpressure, relative
Pressure connection: Flanged, directly on valve body.
Electrical connection: DIN plug
Protection class: IP00 (IP54 with DIN plug mounted)
Housing material: Body: aluminium
Cover: reinforced PBT glassfibre
Ambient temperature: -15...60C
End switch function/capacity: Switch action: 1x SPDT
Resistive: 5A
Inductive (COS PHI = 0.6): 0.5A
Contact Resistance (initial): < 80 mOhm
Approvals: C60VR40 models: CE (EN 1854)
C60VRT40 models: UL
Mounting position: horizontal
DIN plug not included.
Maximum test pressure 2 Bar < 15 minutes.

Models for Europe
Pressure adjustment range: 30...110mbar
Differential pressure: 4...12mbar
Max. pressure: 600mbar


C60VR40300

Honeywell Pressure switch for gas application C60VR

Compact gas pressure switch based on the Kromschroeder DG.C series for mounting on the side position of VQ400 dual valves and VRB00/VR400/V4730 combination gas valves.
The C60VR40xxx has an adjustable setpoint and performs minimum gas pressure supervision in a safe start interlock circuit.
The C60VR40xxx is designed to be fitted directly on the valve body of the applicable gas valve body, using two mounting screws and an O-ring.
Kind of pressure: overpressure, relative
Pressure connection: Flanged, directly on valve body.
Electrical connection: DIN plug
Protection class: IP00 (IP54 with DIN plug mounted)
Housing material: Body: aluminium
Cover: reinforced PBT glassfibre
Ambient temperature: -15...60C
End switch function/capacity: Switch action: 1x SPDT
Resistive: 5A
Inductive (COS PHI = 0.6): 0.5A
Contact Resistance (initial): < 80 mOhm
Approvals: C60VR40 models: CE (EN 1854)
C60VRT40 models: UL
Mounting position: horizontal
DIN plug not included.
Maximum test pressure 2 Bar < 15 minutes.

Models for Europe
Pressure adjustment range: 100...300mbar
Differential pressure: 15...30mbar
Max. pressure: 600mbar


C60VRT40040

Honeywell Pressure switch for gas application C60VR

Compact gas pressure switch based on the Kromschroeder DG.C series for mounting on the side position of VQ400 dual valves and VRB00/VR400/V4730 combination gas valves.
The C60VR40xxx has an adjustable setpoint and performs minimum gas pressure supervision in a safe start interlock circuit.
The C60VR40xxx is designed to be fitted directly on the valve body of the applicable gas valve body, using two mounting screws and an O-ring.
Kind of pressure: overpressure, relative
Pressure connection: Flanged, directly on valve body.
Electrical connection: DIN plug
Protection class: IP00 (IP54 with DIN plug mounted)
Housing material: Body: aluminium
Cover: reinforced PBT glassfibre
Ambient temperature: -15...60C
End switch function/capacity: Switch action: 1x SPDT
Resistive: 5A
Inductive (COS PHI = 0.6): 0.5A
Contact Resistance (initial): < 80 mOhm
Approvals: C60VR40 models: CE (EN 1854)
C60VRT40 models: UL
Mounting position: horizontal
DIN plug not included.
Maximum test pressure 2 Bar < 15 minutes.

Models for USA
Pressure adjustment range: 5...40mbar
Differential pressure: 1.5...2.5mbar
Max. pressure: 600mbar


C7008A1018/U

Honeywell Signal processors, single channel
Rectifying flame rod for 600U

Flame rod assembly. Electrode length: 305 mm (12")



C7008A1034/U

Honeywell Signal processors, single channel
Rectifying flame rod for 600U

Flame rod assembly. Electrode length: 610 mm (24")



C7012A1145/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

Standard models for intermittent operation
Mechanical connection: 3/4" NPT
Ambient temperature: -4...79C
Protection class: IP66
Supply voltage: 110..120 Vac


C7012A1194/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

Standard models for intermittent operation
Mechanical connection: 3/4" NPT
Ambient temperature: -4...79C
Protection class: IP66
Supply voltage: 240 Vac


C7012C1042/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

UL listed explosion proof models for intermittent operation
Mechanical connection: 1" NPT
Ambient temperature: -29...79C
Protection class: NEMA 7
Supply voltage: 110..120 Vac
Comment: Ex approved in USA only


C7012E1104/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

Standard models for continuous operation (with mechanical shutter)
Mechanical connection: 3/4" NPT
Ambient temperature: -29...79C
Protection class: IP66
Supply voltage: 110..120 Vac
Note: Shutter coil voltage: 120V only


C7012E1120/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

Standard models for continuous operation (with mechanical shutter)
Mechanical connection: 1" NPT
Ambient temperature: -40...79C
Protection class: IP66
Supply voltage: 110..120 Vac
Note: Shutter coil voltage: 120V only


C7012E1153/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

Standard models for continuous operation (with mechanical shutter)
Mechanical connection: 3/4" NPT
Ambient temperature: -29...79C
Protection class: IP66
Supply voltage: 240 Vac
Note: Shutter coil voltage: 120V only


C7012E1187/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

Standard models for continuous operation (with mechanical shutter)
Mechanical connection: 3/4" NPT
Ambient temperature: -29...79C
Protection class: IP66
Supply voltage: 220 Vac
Comment: "DIN" version
Note: Shutter coil voltage: 120V only


C7012E1195/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

Standard models for continuous operation (with mechanical shutter)
Mechanical connection: 3/4" NPT
Ambient temperature: -29...79C
Protection class: IP66
Supply voltage: 110 Vac
Comment: "DIN" version
Note: Shutter coil voltage: 120V only


C7012F1052/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

UL listed explosion proof models for continuous operation (with mechanical shutter)
Mechanical connection: 1" NPT
Ambient temperature: -29...79C
Protection class: NEMA 7
Supply voltage: 110..120 Vac
Comment: Ex approved in USA only
Note: Shutter coil voltage: 120V only


C7012G1019/U

Honeywell UV flame sensors C7012A/C/E/F/G

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7012E/F models are approved for use in continuous operation, by using dynamic self-check.
C7012C/F models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models 1" NPT).
The "DIN" models have an additional grounding wire (green/yellow)
Cable length: 2.4m

Standard models for intermittent operation
Mechanical connection: 3/4" NPT
Ambient temperature: -4...79C
Protection class: IP66
Supply voltage: 220 Vac
Comment: "DIN" version


C7027A1023/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7027 with clamp type connector
Mechanical connection: 1/2"
Cable length: 2.4m
Ambient temperature: -18...102C
Protection class: IP54


C7027A1031/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7027 with clamp type connector
Mechanical connection: 1/2"
Cable length: 2.4m
Ambient temperature: -40...102C
Protection class: IP54


C7027A1049/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7027 with 1/2" NPT threaded spud connector
Mechanical connection: 1/2"
Cable length: 2.4m
Ambient temperature: -18...102C
Protection class: IP54


C7027A1056/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7027 with clamp type connector
Mechanical connection: 1/2"
Cable length: 2.4m
Ambient temperature: -18...102C
Protection class: IP54
Comment: "DIN/BG" model


C7027A1064/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7027 with 1/2" NPT threaded spud connector
Mechanical connection: 1/2"
Cable length: 7.3m
Ambient temperature: -40...102C
Protection class: IP54


C7035A1023/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7035 with field replaceable UV tube
Mechanical connection: 1"
Cable length: 1.8m
Ambient temperature: -18...121C
Protection class: IP67


C7035A1031/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7035 with field replaceable UV tube
Mechanical connection: 1"
Cable length: 1.8m
Ambient temperature: -40...121C
Protection class: IP67


C7035A1049/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7035 with field replaceable UV tube
Mechanical connection: 1" BSP
Cable length: 1.8m
Ambient temperature: -18...121C
Protection class: IP67
Comment: "DIN/BG" model


C7035A1056/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7035 with field replaceable UV tube
Mechanical connection: 1"
Cable length: 1.8m
Ambient temperature: -40...121C
Protection class: IP67


C7035A1064/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7035 with field replaceable UV tube
Mechanical connection: 1" BSP
Cable length: 1.8m
Ambient temperature: -40...121C
Protection class: IP67
Comment: "DIN/BG" model


C7035A1080/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7035 with field replaceable UV tube
Mechanical connection: 1"
Cable length: 1.8m
Ambient temperature: -18...121C
Protection class: IP67
Comment: High temp. wires (315C)


C7044A1006/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7044 for side or end viewing
Mechanical connection: mounting bracket
Cable length: 1.8m
Ambient temperature: -18...102C
Protection class: IP54


C7061A1004/U

Honeywell UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7061-series models are approved for use in continuous operation, by using dynamic self-check.
C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply needed.
The "DIN" models have an additional grounding wire (green/yellow)
Ambient temperature: -40...80C

European models for continuous operation, with mechanical shutter
Mechanical connection: 3/4" NPT
Cable length: 2.4m
Protection class: IP66
Comment: "DIN" model, with 5-wire cable
Note: Single shutter coil voltage: 120V only


C7061A1012/U

Honeywell UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7061-series models are approved for use in continuous operation, by using dynamic self-check.
C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply needed.
The "DIN" models have an additional grounding wire (green/yellow)
Ambient temperature: -40...80C

American models for continuous operation, with mechanical shutter
Mechanical connection: 3/4" NPT
Cable length: 2.4m
Protection class: IP66
Note: Single shutter coil voltage: 120V only


C7061A1020/U

Honeywell UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7061-series models are approved for use in continuous operation, by using dynamic self-check.
C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply needed.
The "DIN" models have an additional grounding wire (green/yellow)
Ambient temperature: -40...80C

European models for continuous operation, with mechanical shutter
Mechanical connection: 3/4" NPT
Cable length: 0m
Protection class: IP66
Note: Dual shutter coil voltage: 120/230V


C7061A1061/U

Honeywell UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7061-series models are approved for use in continuous operation, by using dynamic self-check.
C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply needed.
The "DIN" models have an additional grounding wire (green/yellow)
Ambient temperature: -40...80C

American models for continuous operation, with mechanical shutter
Mechanical connection: 3/4" NPT
Cable length: 2.4m
Protection class: IP66
Comment: With focussing lens
Note: Single shutter coil voltage: 120V only


C7061A1079/U

Honeywell UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7061-series models are approved for use in continuous operation, by using dynamic self-check.
C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply needed.
The "DIN" models have an additional grounding wire (green/yellow)
Ambient temperature: -40...80C

European models for continuous operation, with mechanical shutter
Mechanical connection: 3/4" NPT
Cable length: 0m
Protection class: IP66
Comment: With focussing lens
Note: Dual shutter coil voltage: 120/230V


C7061F1003

Honeywell UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7061-series models are approved for use in continuous operation, by using dynamic self-check.
C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply needed.
The "DIN" models have an additional grounding wire (green/yellow)
Ambient temperature: -40...80C

ATEX certified Ex-proof European models for continuous operation, with mechanical shutter (Ex: CENELEC II G Ex d IIC T6; zone 1&2)
Mechanical connection: 1" NPT
Cable length: 0m
Protection class: IP67
Comment: Incl. cable gland
Note: Dual shutter coil voltage: 120/230V


C7061F1011

Honeywell UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7061-series models are approved for use in continuous operation, by using dynamic self-check.
C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply needed.
The "DIN" models have an additional grounding wire (green/yellow)
Ambient temperature: -40...80C

KOSHA approved Ex-proof Korean models for continuous operation, with mechanical shutter (Ex: Ex d IIC T6 IP65)
Mechanical connection: 1" NPT
Cable length: 0m
Protection class: IP65
Comment: Ex-proof in Korea only
Note: Dual shutter coil voltage: 120/230V


C7061F2001/U

Honeywell UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
C7061-series models are approved for use in continuous operation, by using dynamic self-check.
C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply needed.
The "DIN" models have an additional grounding wire (green/yellow)
Ambient temperature: -40...80C

UL listed Ex-proof American models for continuous operation, with mechanical shutter (Ex: Class I, gr.C/D and Class II, gr.E/F/G)
Mechanical connection: 1" NPT
Cable length: 2.4m
Protection class: NEMA 7
Comment: Ex-proof in Americas only
Note: Single shutter coil voltage: 120V only


C7076A1007/U

Honeywell UV flame sensors C7076

UV flame sensor to detect ultraviolet radiation emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications, that use solid fuel or heavy oil, dirty gas, hydrogen, sulphur, etc. as fuel.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
Approved for use in continuous operation, by using dynamic self-check.
Integrated air purge connection.
Quick and easy installation on standard 1" NPT sight pipe.
Note: The C7076F models for use in hazardous areas are discontinued. Functional replacement is the Honeywell U2-101xS-PF series of combination flame sensors. For details, refer to the Industrial Flame Monitoring section from the start of the "Industrial Combustion" pages.
Spare parts for C7076F models (UV sensing tube and shutter coil assembly) remain available.
Mechanical connection: 1" NPT
Ambient temperature: -40...70C
Protection class: IP65
Note: Shutter coil voltage: 120V only

Standard enclosure (IP65)
Supply voltage: 110..120 Vac


C7076A1031/U

Honeywell UV flame sensors C7076

UV flame sensor to detect ultraviolet radiation emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications, that use solid fuel or heavy oil, dirty gas, hydrogen, sulphur, etc. as fuel.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
Approved for use in continuous operation, by using dynamic self-check.
Integrated air purge connection.
Quick and easy installation on standard 1" NPT sight pipe.
Note: The C7076F models for use in hazardous areas are discontinued. Functional replacement is the Honeywell U2-101xS-PF series of combination flame sensors. For details, refer to the Industrial Flame Monitoring section from the start of the "Industrial Combustion" pages.
Spare parts for C7076F models (UV sensing tube and shutter coil assembly) remain available.
Mechanical connection: 1" NPT
Ambient temperature: -40...70C
Protection class: IP65
Note: Shutter coil voltage: 120V only

Standard enclosure (IP65)
Supply voltage: 220..240 Vac


C7076F1006

Honeywell UV flame sensors C7076

UV flame sensor to detect ultraviolet radiation emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications, that use solid fuel or heavy oil, dirty gas, hydrogen, sulphur, etc. as fuel.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
Approved for use in continuous operation, by using dynamic self-check.
Integrated air purge connection.
Quick and easy installation on standard 1" NPT sight pipe.
Note: The C7076F models for use in hazardous areas are discontinued. Functional replacement is the Honeywell U2-101xS-PF series of combination flame sensors. For details, refer to the Industrial Flame Monitoring section from the start of the "Industrial Combustion" pages.
Spare parts for C7076F models (UV sensing tube and shutter coil assembly) remain available.
Mechanical connection: 1" NPT
Ambient temperature: -40...70C
Protection class: IP65
Note: Shutter coil voltage: 120V only

Ex-proof enclosure (ATEX: II G Ex d IIC T6 Zone 1&2)Limited quantities left for use as spare part.
Supply voltage: 220..240 Vac
Comment: Functional repl. U2-1016S-PF


C7076F1014

Honeywell UV flame sensors C7076

UV flame sensor to detect ultraviolet radiation emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications, that use solid fuel or heavy oil, dirty gas, hydrogen, sulphur, etc. as fuel.
Approvals: CE approved according to EN298 only when used with the correct Honeywell flame amplifiers and/or burner controls.
Approved for use in continuous operation, by using dynamic self-check.
Integrated air purge connection.
Quick and easy installation on standard 1" NPT sight pipe.
Note: The C7076F models for use in hazardous areas are discontinued. Functional replacement is the Honeywell U2-101xS-PF series of combination flame sensors. For details, refer to the Industrial Flame Monitoring section from the start of the "Industrial Combustion" pages.
Spare parts for C7076F models (UV sensing tube and shutter coil assembly) remain available.
Mechanical connection: 1" NPT
Ambient temperature: -40...70C
Protection class: IP65
Note: Shutter coil voltage: 120V only

Ex-proof enclosure (ATEX: II G Ex d IIC T6 Zone 1&2)Limited quantities left for use as spare part.
Supply voltage: 110..120 Vac
Comment: Functional repl. U2-1016S-PF


C7927A1016/U

Honeywell UV flame sensors C7027/35/44 ("MiniPeeper")

Compact analogue UV flame sensor to detect ultraviolet radiations emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision for commercial and industrial burner applications.
Approvals: CE approved according to EN298, only when used with the correct Honeywell flame amplifiers and/or burner controls.
UL/CSA approved for USA
AGA approved for Australia
Only for intermittent operation. The burner has to recycle at least once per 24 hours.
Models marked "DIN Approved Model" have no CSA/UL marking on the product label and have an insulated cable instead of wires.
Maximum recommended cable length: ca. 50m
Features: Rugged, compact, with encapsulated sensing tube for maximum protection.
Quick and easy installation on standard sight pipe.

C7927 solid state UV sensor (for EC/RM78xx only)
Mechanical connection: 1/2"
Cable length: 1.8m
Ambient temperature: -18...102C
Protection class: IP54
Comment: Not CE (EN298) approved.


CO020012

Honeywell Safety combination shutoff gas valve with integrated gas pressure regulation
DIN connector (to be ordered separately.

Standard DIN connector, colour black. Order quantity: 10 pcs.



COMPM221

Honeywell Solenoid gas valve, normally closed VE400AA
Electrical connection

DIN Plug, with integrated rectifier (for RAC coil VE400AA versions)



DBC2000E1000

Honeywell Burner Controls DBC2000-series

The Honeywell DBC2000 is a microprocessor-based integrated burner controller for automatically fired gas, oil or combination fuel industrial single burner power burner applications. The DBC2000 system consists of the relay module and wiring subbase. The Standard Model provides the minimum requirements to control an industrial burner system; the Enhanced Model includes an integrated Valve Proofing System.
For all type of burners with unlimited capacity in intermittent operation. An integrated timer assures an automated recycle sequence after ca 24h uninterrupted heat demand.
Approvals: CE approved against EN298:2003 for intermittent operation (when used with correct flame sensor).
For use as spare part only in GAR applications
AGA certified
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
DBC2000 models have two integrated flame amplifiers: UV Power Tube (UV) and Rectification (FR), that are selectable by a jumper at the back of the unit. Default is FR (jumper present). Applicable flame sensors:
Flame rod (FR)
UV sensor family C7027/35/44 (UV)
UV sensor family C7012A/G (FR)
Note: Extra features:
Integrated 24h auto recycle timer
Selectable Pilot or Direct Main Burner Ignition operation.
Selectable post-purge (15s) or no-post-purge (0s) operation.
Control model: Full
Outputs: HF/LF/Modulate
Operation: 24h auto-recycle
Pilot: Selectable intermittent / interrupted
Pilot ignition time: 3s (Pilot only: 5s)
Main ignition time: 3s
Post purge time: 15/0s
Number of ignition attempts: 1
Flame failure response time: <1s
Flame detector: UV/FR

115Vac versions
Prepurge time: 35s
Valve proofing system: no
Comment: Standard Model


DBC2000E1018

Honeywell Burner Controls DBC2000-series

The Honeywell DBC2000 is a microprocessor-based integrated burner controller for automatically fired gas, oil or combination fuel industrial single burner power burner applications. The DBC2000 system consists of the relay module and wiring subbase. The Standard Model provides the minimum requirements to control an industrial burner system; the Enhanced Model includes an integrated Valve Proofing System.
For all type of burners with unlimited capacity in intermittent operation. An integrated timer assures an automated recycle sequence after ca 24h uninterrupted heat demand.
Approvals: CE approved against EN298:2003 for intermittent operation (when used with correct flame sensor).
For use as spare part only in GAR applications
AGA certified
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
DBC2000 models have two integrated flame amplifiers: UV Power Tube (UV) and Rectification (FR), that are selectable by a jumper at the back of the unit. Default is FR (jumper present). Applicable flame sensors:
Flame rod (FR)
UV sensor family C7027/35/44 (UV)
UV sensor family C7012A/G (FR)
Note: Extra features:
Integrated 24h auto recycle timer
Selectable Pilot or Direct Main Burner Ignition operation.
Selectable post-purge (15s) or no-post-purge (0s) operation.
Control model: Full
Outputs: HF/LF/Modulate
Operation: 24h auto-recycle
Pilot: Selectable intermittent / interrupted
Pilot ignition time: 3s (Pilot only: 5s)
Main ignition time: 3s
Post purge time: 15/0s
Number of ignition attempts: 1
Flame failure response time: <1s
Flame detector: UV/FR

230Vac versions
Prepurge time: 35s
Valve proofing system: no
Comment: Standard Model


DBC2000E1018-IE

Honeywell Burner Controls DBC2000-series

The Honeywell DBC2000 is a microprocessor-based integrated burner controller for automatically fired gas, oil or combination fuel industrial single burner power burner applications. The DBC2000 system consists of the relay module and wiring subbase. The Standard Model provides the minimum requirements to control an industrial burner system; the Enhanced Model includes an integrated Valve Proofing System.
For all type of burners with unlimited capacity in intermittent operation. An integrated timer assures an automated recycle sequence after ca 24h uninterrupted heat demand.
Approvals: CE approved against EN298:2003 for intermittent operation (when used with correct flame sensor).
For use as spare part only in GAR applications
AGA certified
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
DBC2000 models have two integrated flame amplifiers: UV Power Tube (UV) and Rectification (FR), that are selectable by a jumper at the back of the unit. Default is FR (jumper present). Applicable flame sensors:
Flame rod (FR)
UV sensor family C7027/35/44 (UV)
UV sensor family C7012A/G (FR)
Note: Extra features:
Integrated 24h auto recycle timer
Selectable Pilot or Direct Main Burner Ignition operation.
Selectable post-purge (15s) or no-post-purge (0s) operation.
Control model: Full
Outputs: HF/LF/Modulate
Operation: 24h auto-recycle
Pilot: Selectable intermittent / interrupted
Pilot ignition time: 3s (Pilot only: 5s)
Main ignition time: 3s
Post purge time: 15/0s
Number of ignition attempts: 1
Flame failure response time: <1s
Flame detector: UV/FR

230Vac versions
Prepurge time: 60s
Valve proofing system: no
Comment: Standard Model


DBC2000E1026

Honeywell Burner Controls DBC2000-series

The Honeywell DBC2000 is a microprocessor-based integrated burner controller for automatically fired gas, oil or combination fuel industrial single burner power burner applications. The DBC2000 system consists of the relay module and wiring subbase. The Standard Model provides the minimum requirements to control an industrial burner system; the Enhanced Model includes an integrated Valve Proofing System.
For all type of burners with unlimited capacity in intermittent operation. An integrated timer assures an automated recycle sequence after ca 24h uninterrupted heat demand.
Approvals: CE approved against EN298:2003 for intermittent operation (when used with correct flame sensor).
For use as spare part only in GAR applications
AGA certified
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
DBC2000 models have two integrated flame amplifiers: UV Power Tube (UV) and Rectification (FR), that are selectable by a jumper at the back of the unit. Default is FR (jumper present). Applicable flame sensors:
Flame rod (FR)
UV sensor family C7027/35/44 (UV)
UV sensor family C7012A/G (FR)
Note: Extra features:
Integrated 24h auto recycle timer
Selectable Pilot or Direct Main Burner Ignition operation.
Selectable post-purge (15s) or no-post-purge (0s) operation.
Control model: Full
Outputs: HF/LF/Modulate
Operation: 24h auto-recycle
Pilot: Selectable intermittent / interrupted
Pilot ignition time: 3s (Pilot only: 5s)
Main ignition time: 3s
Post purge time: 15/0s
Number of ignition attempts: 1
Flame failure response time: <1s
Flame detector: UV/FR

230Vac versions
Prepurge time: 0s
Valve proofing system: no
Comment: Standard Model


DBC2000E1034

Honeywell Burner Controls DBC2000-series

The Honeywell DBC2000 is a microprocessor-based integrated burner controller for automatically fired gas, oil or combination fuel industrial single burner power burner applications. The DBC2000 system consists of the relay module and wiring subbase. The Standard Model provides the minimum requirements to control an industrial burner system; the Enhanced Model includes an integrated Valve Proofing System.
For all type of burners with unlimited capacity in intermittent operation. An integrated timer assures an automated recycle sequence after ca 24h uninterrupted heat demand.
Approvals: CE approved against EN298:2003 for intermittent operation (when used with correct flame sensor).
For use as spare part only in GAR applications
AGA certified
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
DBC2000 models have two integrated flame amplifiers: UV Power Tube (UV) and Rectification (FR), that are selectable by a jumper at the back of the unit. Default is FR (jumper present). Applicable flame sensors:
Flame rod (FR)
UV sensor family C7027/35/44 (UV)
UV sensor family C7012A/G (FR)
Note: Extra features:
Integrated 24h auto recycle timer
Selectable Pilot or Direct Main Burner Ignition operation.
Selectable post-purge (15s) or no-post-purge (0s) operation.
Control model: Full
Outputs: HF/LF/Modulate
Operation: 24h auto-recycle
Pilot: Selectable intermittent / interrupted
Pilot ignition time: 3s (Pilot only: 5s)
Main ignition time: 3s
Post purge time: 15/0s
Number of ignition attempts: 1
Flame failure response time: <1s
Flame detector: UV/FR

230Vac versions
Prepurge time: 60s
Valve proofing system: no
Comment: Standard Model


DBC2000E2001

Honeywell Burner Controls DBC2000-series

The Honeywell DBC2000 is a microprocessor-based integrated burner controller for automatically fired gas, oil or combination fuel industrial single burner power burner applications. The DBC2000 system consists of the relay module and wiring subbase. The Standard Model provides the minimum requirements to control an industrial burner system; the Enhanced Model includes an integrated Valve Proofing System.
For all type of burners with unlimited capacity in intermittent operation. An integrated timer assures an automated recycle sequence after ca 24h uninterrupted heat demand.
Approvals: CE approved against EN298:2003 for intermittent operation (when used with correct flame sensor).
For use as spare part only in GAR applications
AGA certified
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
DBC2000 models have two integrated flame amplifiers: UV Power Tube (UV) and Rectification (FR), that are selectable by a jumper at the back of the unit. Default is FR (jumper present). Applicable flame sensors:
Flame rod (FR)
UV sensor family C7027/35/44 (UV)
UV sensor family C7012A/G (FR)
Note: Extra features:
Integrated 24h auto recycle timer
Selectable Pilot or Direct Main Burner Ignition operation.
Selectable post-purge (15s) or no-post-purge (0s) operation.
Control model: Full
Outputs: HF/LF/Modulate
Operation: 24h auto-recycle
Pilot: Selectable intermittent / interrupted
Pilot ignition time: 3s (Pilot only: 5s)
Main ignition time: 3s
Post purge time: 15/0s
Number of ignition attempts: 1
Flame failure response time: <1s
Flame detector: UV/FR

115Vac versions
Prepurge time: 35s
Valve proofing system: Integrated
Comment: Enhanced Model


DBC2000E2019

Honeywell Burner Controls DBC2000-series

The Honeywell DBC2000 is a microprocessor-based integrated burner controller for automatically fired gas, oil or combination fuel industrial single burner power burner applications. The DBC2000 system consists of the relay module and wiring subbase. The Standard Model provides the minimum requirements to control an industrial burner system; the Enhanced Model includes an integrated Valve Proofing System.
For all type of burners with unlimited capacity in intermittent operation. An integrated timer assures an automated recycle sequence after ca 24h uninterrupted heat demand.
Approvals: CE approved against EN298:2003 for intermittent operation (when used with correct flame sensor).
For use as spare part only in GAR applications
AGA certified
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
DBC2000 models have two integrated flame amplifiers: UV Power Tube (UV) and Rectification (FR), that are selectable by a jumper at the back of the unit. Default is FR (jumper present). Applicable flame sensors:
Flame rod (FR)
UV sensor family C7027/35/44 (UV)
UV sensor family C7012A/G (FR)
Note: Extra features:
Integrated 24h auto recycle timer
Selectable Pilot or Direct Main Burner Ignition operation.
Selectable post-purge (15s) or no-post-purge (0s) operation.
Control model: Full
Outputs: HF/LF/Modulate
Operation: 24h auto-recycle
Pilot: Selectable intermittent / interrupted
Pilot ignition time: 3s (Pilot only: 5s)
Main ignition time: 3s
Post purge time: 15/0s
Number of ignition attempts: 1
Flame failure response time: <1s
Flame detector: UV/FR

230Vac versions
Prepurge time: 35s
Valve proofing system: Integrated
Comment: Enhanced Model


EC7820A1026/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 230Vac (EC78xx)
Control model: Atmosferic
Outputs: LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 5/10s
Main ignition time: 5/10s
Post purge time: no
Number of ignition attempts: 1
Flame failure response time: 1,0/2,0s
Valve proofing system: no


EC7820A1034/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 230Vac (EC78xx)
Control model: Atmosferic
Outputs: LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 5/10s
Main ignition time: 5/10s
Post purge time: no
Number of ignition attempts: 3
Flame failure response time: 1,0/2,0s
Valve proofing system: no


EC7823A1004/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

Flame switch only (no program sequence). 230Vac models.
Control model: Flame switch
Outputs: 2xSPDT
Operation: Cont.
Pilot: no
Prepurge timer: no
Pilot ignition time: no
Main ignition time: no
Post purge time: no
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


EC7840L1014/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 230Vac (EC78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Interrupted
Prepurge timer: yes
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: 15s
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


EC7850A1064/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 230Vac (EC78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 3/5s
Main ignition time: 3/5s
Post purge time: 15s
Number of ignition attempts: 1
Flame failure response time: 1,0/2,0s
Valve proofing system: no


EC7850A1072/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 230Vac (EC78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 3/5s
Main ignition time: 3/5s
Post purge time: 2s
Number of ignition attempts: 1
Flame failure response time: 1,0/2,0s
Valve proofing system: no


EC7850A1080/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 230Vac (EC78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 3/5s
Main ignition time: 3/5s
Post purge time: 30s
Number of ignition attempts: 1
Flame failure response time: 1,0/2,0s
Valve proofing system: no


EC7850A1122/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 230Vac (EC78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 3/5s
Main ignition time: 3/5s
Post purge time: 15s
Number of ignition attempts: 1
Flame failure response time: 1,0/2,0s
Valve proofing system: no


EC7890A1011/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 230Vac (EC78xx)
Control model: Primary
Outputs: no
Operation: Intermit.
Pilot: Intermittent
Prepurge timer: no
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: no
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no
Comment: No shutter check


EC7890B1010/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 230Vac (EC78xx)
Control model: Primary
Outputs: no
Operation: Cont.
Pilot: Intermittent
Prepurge timer: no
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: no
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


EC7890B1028/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 230Vac (EC78xx)
Control model: Primary
Outputs: on/off
Operation: Cont.
Pilot: Intermittent
Prepurge timer: no
Pilot ignition time: 5/10s
Main ignition time: no
Post purge time: no
Number of ignition attempts: selectable
Flame failure response time: 1,0/2,0s
Valve proofing system: no


EG1033AA01/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Amplifier modules
Model: Transistor open collector output
Supply voltage: 24..28 Vdc
Temperature range: 0...55C
Maximum humidity: 90%rh
Approvals: no


EG1033AB02/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Amplifier modules
Model: SPST normally closed contact
Supply voltage: 115 Vac
Temperature range: 0...55C
Maximum humidity: 90%rh
Approvals: no


EG1033AC01/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Amplifier modules
Model: SPST normally open contact
Supply voltage: 24..28 Vdc
Temperature range: 0...55C
Maximum humidity: 90%rh
Approvals: no


EG1033AD01/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Amplifier modules
Model: SPST normally closed contact
Supply voltage: 24..28 Vdc
Temperature range: 0...55C
Maximum humidity: 90%rh
Approvals: no


FASA-GLASS

Honeywell Fibre optics extensions for viewing heads

The Honeywell FASA-GLASS and FASA-QUARTZ fibre optic extensions are complete engineered assembled and tested accessories for viewing heads and make it possible to monitor flame in a hostile environment, in the presence of:
excessive vibration
intense heat
corrosive chemicals
explosive gases or dust
complex burner configuration
A fibre optic bundle is used to transmit flame radiation to the remotely located flame detector/viewing head. Flexible stainless steel tubes enclose the fibre optic bundle with forced air injection for cooling.
A lens is used to focus the flame to one end of the fibre optic bundle, with the other end coupled directly to the viewing head.
Various lengths are available in 1 Ft (30.4 cm) incrementals to a maximum of a little less than 8 m (25 Ft)
For IR only detection systems the glass fibre extensions are used
For UV only and dual UV/IR detection systems the quartz fibre extensions are used
Temperature range: -40...400C
Note: FASA fibre optics assemblies are configured products. That means that the full length and used viewing head needs to be specified when ordering. The configuration cannot be changed once the FASA fibre optics assembly has been produced in the factory. Contact Honeywell before ordering.

Infrared: complete glass fibre optics assembly.
Model: IR
Product description: Glass fibre optics complete assembly for IR with guide pipes and flexible connection.


FASA-INT-GLASS

Honeywell Fibre optics extensions for viewing heads

The Honeywell FASA-GLASS and FASA-QUARTZ fibre optic extensions are complete engineered assembled and tested accessories for viewing heads and make it possible to monitor flame in a hostile environment, in the presence of:
excessive vibration
intense heat
corrosive chemicals
explosive gases or dust
complex burner configuration
A fibre optic bundle is used to transmit flame radiation to the remotely located flame detector/viewing head. Flexible stainless steel tubes enclose the fibre optic bundle with forced air injection for cooling.
A lens is used to focus the flame to one end of the fibre optic bundle, with the other end coupled directly to the viewing head.
Various lengths are available in 1 Ft (30.4 cm) incrementals to a maximum of a little less than 8 m (25 Ft)
For IR only detection systems the glass fibre extensions are used
For UV only and dual UV/IR detection systems the quartz fibre extensions are used
Temperature range: -40...400C
Note: FASA fibre optics assemblies are configured products. That means that the full length and used viewing head needs to be specified when ordering. The configuration cannot be changed once the FASA fibre optics assembly has been produced in the factory. Contact Honeywell before ordering.

Infrared: inner assembly glass fibre optics. Excluding outer tubing.
Model: IR
Product description: Glass fibre optics inner assembly for IR with flexible connection.


FASA-INT-QUARTZ

Honeywell Fibre optics extensions for viewing heads

The Honeywell FASA-GLASS and FASA-QUARTZ fibre optic extensions are complete engineered assembled and tested accessories for viewing heads and make it possible to monitor flame in a hostile environment, in the presence of:
excessive vibration
intense heat
corrosive chemicals
explosive gases or dust
complex burner configuration
A fibre optic bundle is used to transmit flame radiation to the remotely located flame detector/viewing head. Flexible stainless steel tubes enclose the fibre optic bundle with forced air injection for cooling.
A lens is used to focus the flame to one end of the fibre optic bundle, with the other end coupled directly to the viewing head.
Various lengths are available in 1 Ft (30.4 cm) incrementals to a maximum of a little less than 8 m (25 Ft)
For IR only detection systems the glass fibre extensions are used
For UV only and dual UV/IR detection systems the quartz fibre extensions are used
Temperature range: -40...400C
Note: FASA fibre optics assemblies are configured products. That means that the full length and used viewing head needs to be specified when ordering. The configuration cannot be changed once the FASA fibre optics assembly has been produced in the factory. Contact Honeywell before ordering.

Ultraviolet: inner assembly quartz fibre optics. Excluding outer tubing.
Model: UV/IR
Product description: Quartz fibre optics complete assembly for UV and/or IR with flexible connection.


FASA-QUARTZ

Honeywell Fibre optics extensions for viewing heads

The Honeywell FASA-GLASS and FASA-QUARTZ fibre optic extensions are complete engineered assembled and tested accessories for viewing heads and make it possible to monitor flame in a hostile environment, in the presence of:
excessive vibration
intense heat
corrosive chemicals
explosive gases or dust
complex burner configuration
A fibre optic bundle is used to transmit flame radiation to the remotely located flame detector/viewing head. Flexible stainless steel tubes enclose the fibre optic bundle with forced air injection for cooling.
A lens is used to focus the flame to one end of the fibre optic bundle, with the other end coupled directly to the viewing head.
Various lengths are available in 1 Ft (30.4 cm) incrementals to a maximum of a little less than 8 m (25 Ft)
For IR only detection systems the glass fibre extensions are used
For UV only and dual UV/IR detection systems the quartz fibre extensions are used
Temperature range: -40...400C
Note: FASA fibre optics assemblies are configured products. That means that the full length and used viewing head needs to be specified when ordering. The configuration cannot be changed once the FASA fibre optics assembly has been produced in the factory. Contact Honeywell before ordering.

Ultraviolet: complete quartz fibre optics assembly.
Model: UV/IR
Product description: Quartz fibre optics complete assembly for UV and/or IR with guide pipes and flexible connection.


FLAMETOOLS-HMI/U

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - programming and monitoring tools

Configuration colour touch screen display, with preinstalled Windows CE based configuration software and Modbus connection to connect 700xCSP, P222, P5xx and U2-S signal processors



FLAMETOOLS-PC

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - programming and monitoring tools

Configuration software on USB key drive, incl. RS422/85 to USB converter module



GHE1-3

Honeywell Heavy duty gas pilot ignitors

The GHE igniters are non-fouling, inextinguishable, high-energy electric igniters suitable for most liquid and gaseous fuels. They are available for both 47 mm (1-7/8") and 73 mm (2-7/8") diameter support tubes, in lengths to suit the application.
The unique high energy circuit makes use of a controlled capacitor discharge to produce a high energy spark at a pulse rate of approximately 3 to 5 times per second that ignites liquid or gaseous fuels more reliably and consistently.
The GHE igniter assembly is comprised of two major parts; a high energy source of ignition and an internal mix air-gas delivery system.
The GHE Igniters are supplied with:
0.9 m (36") stainless steel flexible gas hose
0.9 m (36") stainless steel flexible air hose
burner mounting tube
high energy probe
igniter tip 305 mm (12") long x 12.7 mm (1/2") outer diameter
Various lengths are available in 1 Ft (30.4 cm) incremental to a maximum of 25 Ft (ca. 8 m)
Note: GHE pilot burner assemblies are configured products. That means that the full length needs to be specified when ordering. The configuration cannot be changed once the GHE pilot burner assembly has been produced in the factory. Contact Honeywell before ordering.


Product description: Gas pilot ignitor assembly (300 - 900 kW)


GHE2-5

Honeywell Heavy duty gas pilot ignitors

The GHE igniters are non-fouling, inextinguishable, high-energy electric igniters suitable for most liquid and gaseous fuels. They are available for both 47 mm (1-7/8") and 73 mm (2-7/8") diameter support tubes, in lengths to suit the application.
The unique high energy circuit makes use of a controlled capacitor discharge to produce a high energy spark at a pulse rate of approximately 3 to 5 times per second that ignites liquid or gaseous fuels more reliably and consistently.
The GHE igniter assembly is comprised of two major parts; a high energy source of ignition and an internal mix air-gas delivery system.
The GHE Igniters are supplied with:
0.9 m (36") stainless steel flexible gas hose
0.9 m (36") stainless steel flexible air hose
burner mounting tube
high energy probe
igniter tip 305 mm (12") long x 12.7 mm (1/2") outer diameter
Various lengths are available in 1 Ft (30.4 cm) incremental to a maximum of 25 Ft (ca. 8 m)
Note: GHE pilot burner assemblies are configured products. That means that the full length needs to be specified when ordering. The configuration cannot be changed once the GHE pilot burner assembly has been produced in the factory. Contact Honeywell before ordering.


Product description: Gas pilot ignitor assembly (600 - 1500 kW)


HFVR050

Honeywell Combination valve "VQ-Modular' with or without side valves
Fine particle filter, for mounting on inlet side (to be ordered separately)

Filter size 50 micron. Pack size 10pcs.



HFVR150

Honeywell Combination valve "VQ-Modular' with or without side valves
Fine particle filter, for mounting on inlet side (to be ordered separately)

Filter size 150 micron. Pack size 10pcs.



HTS-pdf-Catalogue

Honeywell Honeywell Thermal Solutions Product Catalogue

These pages show an overview and offer downloads of data sheets and certificates of the Honeywell branded Thermal Solutions products and solutions that are available for ordering through the Honeywell Europe sales channels, such as:
SLATETM burner/boiler management system
EC/RM7800-series "Blue Line" burner controllers
C7xxx-series optical flame sensors
IFM industrial flame monitoring products (former "IRIS Systems Inc.")
VE-series solenoid valves
C6097 gas pressure switches
and more...
Note: Kromschroeder is now part of Honeywell. An overview of and downloads for the Kromschroeder branded Thermal Solutions products can be found in Docuthek.
Please visit:: http://www.docuthek.com


Comment: Download printable catalogue


HV-HT

Honeywell Heavy duty gas pilot ignitors
Replacement parts

Replacement internal GHE igniter cable with contact, specify length before ordering.



IGN-CPC-LB

Honeywell Heavy duty gas pilot ignitors
Replacement parts

Replacement igniter probe junction box with canon plug receptacle for GHE igniters.



ISO-OR

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - various parts

Replacement O-ring for ISO-UNIT, ISO-UNITSS and ISO-UNITHPGT



ISO-QW

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - various parts

Replacement quartz window for ISO-Unit and ISO-UnitSS



ISO-RR

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - various parts

Replacement retainer ring for ISO-UNIT, ISO-UNITSS and ISO-UNITHPGT



ISO-UNIT

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1" NPTF sealing union with quartz window and 1/2" NPTF purge port



ISO-UNITHPGT

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1" NPTF sealing union with quartz window and 1/2" NPTF purge port. High pressure version with 1/2" thick high pressure quartz window



ISO-UNITSS

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1" NPTF stainless steel sealing union with quartz window and 1/2" NPTF purge port



ISO-WRENCH

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - various parts

ISO-Union wrench set.



Installation

Honeywell Intelligent safety combination shutoff gas valve with integrated smart technology

The "Vulcan" SV2 Series servo regulated combination valves are used for control and regulation of gaseous fuels in gas fired power burners, atmospheric gas boilers, melting furnaces, incinerators and other gas consuming appliances. These smart combination valves are available in various configurations from 3/4" up to 3". the following different versions:
Designed for but not limited to commercial burner and boiler applications
Gas valve type: Class A safety shut-off valves
Port connection: flanges
Media: Natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE, UL, CSA
Note: Contact a Honeywell Thermal Solutions Representative for more information.
Supply voltage: 24/120/230 Vac

Downloads
Comment: Installation Instructions


KTCOMB15

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits without screen, for mounting on outlet side (to be ordered separately)

Flange kit for VQ420/25M. Contains 2x Rp 1/2"



KTCOMB20

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits without screen, for mounting on outlet side (to be ordered separately)

Flange kit for VQ420/25M. Contains 2x Rp 3/4"



KTCOMB25

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits without screen, for mounting on outlet side (to be ordered separately)

Flange kit for VQ420/25M. Contains 2x Rp 1"



KTCOMB32

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits without screen, for mounting on outlet side (to be ordered separately)

Flange kit for VQ440/50M. Contains 2x Rp 1 1/4"



KTCOMB40

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits without screen, for mounting on outlet side (to be ordered separately)

Flange kit for VQ440/50M. Contains 2x Rp 1 1/2"



KTCOMB50

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits without screen, for mounting on outlet side (to be ordered separately)

Flange kit for VQ440/50M. Contains 2x Rp 2"



KTCOMS15

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits with screen, for mounting on inlet side (to be ordered separately)

Flange kit for VQ420/25M. Contains 2x Rp 1/2"



KTCOMS20

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits with screen, for mounting on inlet side (to be ordered separately)

Flange kit for VQ420/25M. Contains 2x Rp 3/4"



KTCOMS25

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits with screen, for mounting on inlet side (to be ordered separately)

Flange kit for VQ420/25M. Contains 2x Rp 1"



KTCOMS32

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits with screen, for mounting on inlet side (to be ordered separately)

Flange kit for VQ440/50M. Contains 2x Rp 1 1/4"



KTCOMS40

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits with screen, for mounting on inlet side (to be ordered separately)

Flange kit for VQ440/50M. Contains 2x Rp 1 1/2"



KTCOMS50

Honeywell Combination valve "VQ-Modular' with or without side valves
Flange kits with screen, for mounting on inlet side (to be ordered separately)

Flange kit for VQ440/50M. Contains 2x Rp 2"



KTCPI001

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1
Accessories

Visual Closed Position Indicator



KTGRFR01

Honeywell Combination valve "VQ-Modular' with or without side valves
Replacement parts

Replacement retarder for VE4xxxC-series DN10..25 and VQ4xxMC-series DN20-DN25



KTGRFR02

Honeywell Combination valve "VQ-Modular' with or without side valves
Replacement parts

Replacement retarder for VE4xxxC-series DN32..50 and VQ4xxMC-series DN40-DN40



L404F1060/U

Honeywell Pressuretrol Controllers

Provide operating control with automatic limit protection for pressure systems up to 20 Bar (300 psi).
Kind of pressure: overpressure, relative
Electrical connection: conduit
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: -37...66C
Ambient temperature: -37...66C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 1 A (inductive); 5 A resistive
Mounting position: vertical
Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element
Models have snap-acting switching to open or close a circuit on pressure rise
Adjustable differentials
Mount using 1/4" NPT internal pipe thread or surface mount through base of case
Stainless steel diaphragm

American model
Pressure adjustment range: 14...103kPa
Differential pressure adjustment range: 14...41kPa
Max. pressure: 345kPa
Pressure connection: 1/4" NPT
Protection class: NEMA1


L404F1078/U

Honeywell Pressuretrol Controllers

Provide operating control with automatic limit protection for pressure systems up to 20 Bar (300 psi).
Kind of pressure: overpressure, relative
Electrical connection: conduit
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: -37...66C
Ambient temperature: -37...66C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 1 A (inductive); 5 A resistive
Mounting position: vertical
Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element
Models have snap-acting switching to open or close a circuit on pressure rise
Adjustable differentials
Mount using 1/4" NPT internal pipe thread or surface mount through base of case
Stainless steel diaphragm

American model
Pressure adjustment range: 35...345kPa
Differential pressure adjustment range: 41...97kPa
Max. pressure: 586kPa
Pressure connection: 1/4" NPT
Protection class: NEMA1


L404F1094/U

Honeywell Pressuretrol Controllers

Provide operating control with automatic limit protection for pressure systems up to 20 Bar (300 psi).
Kind of pressure: overpressure, relative
Electrical connection: conduit
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: -37...66C
Ambient temperature: -37...66C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 1 A (inductive); 5 A resistive
Mounting position: vertical
Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element
Models have snap-acting switching to open or close a circuit on pressure rise
Adjustable differentials
Mount using 1/4" NPT internal pipe thread or surface mount through base of case
Stainless steel diaphragm

American model
Pressure adjustment range: 138...2068kPa
Differential pressure adjustment range: 138...345kPa
Max. pressure: 2413kPa
Pressure connection: 1/4" NPT
Protection class: NEMA1


L404F1102/U

Honeywell Pressuretrol Controllers

Provide operating control with automatic limit protection for pressure systems up to 20 Bar (300 psi).
Kind of pressure: overpressure, relative
Electrical connection: conduit
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: -37...66C
Ambient temperature: -37...66C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 1 A (inductive); 5 A resistive
Mounting position: vertical
Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element
Models have snap-acting switching to open or close a circuit on pressure rise
Adjustable differentials
Mount using 1/4" NPT internal pipe thread or surface mount through base of case
Stainless steel diaphragm

American model
Pressure adjustment range: 69...1034kPa
Differential pressure adjustment range: 60...152kPa
Max. pressure: 1551kPa
Pressure connection: 1/4" NPT
Protection class: NEMA1


L404F1219/U

Honeywell Pressuretrol Controllers

Provide operating control with automatic limit protection for pressure systems up to 20 Bar (300 psi).
Kind of pressure: overpressure, relative
Electrical connection: conduit
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: -37...66C
Ambient temperature: -37...66C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 1 A (inductive); 5 A resistive
Mounting position: vertical
Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element
Models have snap-acting switching to open or close a circuit on pressure rise
Adjustable differentials
Mount using 1/4" NPT internal pipe thread or surface mount through base of case
Stainless steel diaphragm

European model, incl. grounding screw
Pressure adjustment range: 14...103kPa
Differential pressure adjustment range: 14...41kPa
Max. pressure: 345kPa
Pressure connection: 1/4" BSP
Protection class: IP40


L404F1227/U

Honeywell Pressuretrol Controllers

Provide operating control with automatic limit protection for pressure systems up to 20 Bar (300 psi).
Kind of pressure: overpressure, relative
Electrical connection: conduit
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: -37...66C
Ambient temperature: -37...66C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 1 A (inductive); 5 A resistive
Mounting position: vertical
Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element
Models have snap-acting switching to open or close a circuit on pressure rise
Adjustable differentials
Mount using 1/4" NPT internal pipe thread or surface mount through base of case
Stainless steel diaphragm

European model, incl. grounding screw
Pressure adjustment range: 69...1034kPa
Differential pressure adjustment range: 60...152kPa
Max. pressure: 1551kPa
Pressure connection: 1/4" BSP
Protection class: IP40


L404F1235/U

Honeywell Pressuretrol Controllers

Provide operating control with automatic limit protection for pressure systems up to 20 Bar (300 psi).
Kind of pressure: overpressure, relative
Electrical connection: conduit
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: -37...66C
Ambient temperature: -37...66C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 1 A (inductive); 5 A resistive
Mounting position: vertical
Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element
Models have snap-acting switching to open or close a circuit on pressure rise
Adjustable differentials
Mount using 1/4" NPT internal pipe thread or surface mount through base of case
Stainless steel diaphragm

European model, incl. grounding screw
Pressure adjustment range: 138...2068kPa
Differential pressure adjustment range: 138...345kPa
Max. pressure: 2413kPa
Pressure connection: 1/4" BSP
Protection class: IP40


L404F1243/U

Honeywell Pressuretrol Controllers

Provide operating control with automatic limit protection for pressure systems up to 20 Bar (300 psi).
Kind of pressure: overpressure, relative
Electrical connection: conduit
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: -37...66C
Ambient temperature: -37...66C
Switch function/capacity: SPDT Microswitch 250Vac; capacity: 1 A (inductive); 5 A resistive
Mounting position: vertical
Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element
Models have snap-acting switching to open or close a circuit on pressure rise
Adjustable differentials
Mount using 1/4" NPT internal pipe thread or surface mount through base of case
Stainless steel diaphragm

European model, incl. grounding screw
Pressure adjustment range: 35...345kPa
Differential pressure adjustment range: 41...97kPa
Max. pressure: 586kPa
Pressure connection: 1/4" BSP
Protection class: IP40


L91B1035/U

Honeywell Proportional Pressuretrol Controllers

Modulating pressure operating control for regulation of liquid or air and other non-corrosive gases.
Kind of pressure: overpressure, relative
Pressure connection: 1/4" NPT external thread
Electrical connection: conduit
Protection class: IP44
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: 0...66C
Ambient temperature: 0...66C
Switch function/capacity: Modulating: 140 Ohm potentimeter
Mounting position: vertical
Brass bellows
Use with steam, air, noncombustible gases, or other fluids noncorrosive to the brass or phos-bronze (20 Bar / 300 psi models) bellows
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)

Single potentiometer 140 Ohms. With optional surface mount through back of case.
Pressure adjustment range: 0...103kPa
Differential pressure adjustment range: 10...83kPa
Max. pressure: 172kPa


L91B1050/U

Honeywell Proportional Pressuretrol Controllers

Modulating pressure operating control for regulation of liquid or air and other non-corrosive gases.
Kind of pressure: overpressure, relative
Pressure connection: 1/4" NPT external thread
Electrical connection: conduit
Protection class: IP44
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: 0...66C
Ambient temperature: 0...66C
Switch function/capacity: Modulating: 140 Ohm potentimeter
Mounting position: vertical
Brass bellows
Use with steam, air, noncombustible gases, or other fluids noncorrosive to the brass or phos-bronze (20 Bar / 300 psi models) bellows
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)

Single potentiometer 140 Ohms. With optional surface mount through back of case.
Pressure adjustment range: 34...1034kPa
Differential pressure adjustment range: 35...160kPa
Max. pressure: 1551kPa


L91B1068/U

Honeywell Proportional Pressuretrol Controllers

Modulating pressure operating control for regulation of liquid or air and other non-corrosive gases.
Kind of pressure: overpressure, relative
Pressure connection: 1/4" NPT external thread
Electrical connection: conduit
Protection class: IP44
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: 0...66C
Ambient temperature: 0...66C
Switch function/capacity: Modulating: 140 Ohm potentimeter
Mounting position: vertical
Brass bellows
Use with steam, air, noncombustible gases, or other fluids noncorrosive to the brass or phos-bronze (20 Bar / 300 psi models) bellows
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)

Single potentiometer 140 Ohms. With optional surface mount through back of case.
Pressure adjustment range: 69...2068kPa
Differential pressure adjustment range: 193...758kPa
Max. pressure: 2241kPa


L91B1100/U

Honeywell Proportional Pressuretrol Controllers

Modulating pressure operating control for regulation of liquid or air and other non-corrosive gases.
Kind of pressure: overpressure, relative
Pressure connection: 1/4" NPT external thread
Electrical connection: conduit
Protection class: IP44
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: 0...66C
Ambient temperature: 0...66C
Switch function/capacity: Modulating: 140 Ohm potentimeter
Mounting position: vertical
Brass bellows
Use with steam, air, noncombustible gases, or other fluids noncorrosive to the brass or phos-bronze (20 Bar / 300 psi models) bellows
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)

Single potentiometer 140 Ohms. With G1/4" mounting.
Pressure adjustment range: 0...1034kPa
Differential pressure adjustment range: 35...160kPa
Max. pressure: 1551kPa


L91B1118/U

Honeywell Proportional Pressuretrol Controllers

Modulating pressure operating control for regulation of liquid or air and other non-corrosive gases.
Kind of pressure: overpressure, relative
Pressure connection: 1/4" NPT external thread
Electrical connection: conduit
Protection class: IP44
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: 0...66C
Ambient temperature: 0...66C
Switch function/capacity: Modulating: 140 Ohm potentimeter
Mounting position: vertical
Brass bellows
Use with steam, air, noncombustible gases, or other fluids noncorrosive to the brass or phos-bronze (20 Bar / 300 psi models) bellows
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)

Single potentiometer 140 Ohms. With G1/4" mounting.
Pressure adjustment range: 0...2068kPa
Differential pressure adjustment range: 193...758kPa
Max. pressure: 2241kPa


L91B1241/U

Honeywell Proportional Pressuretrol Controllers

Modulating pressure operating control for regulation of liquid or air and other non-corrosive gases.
Kind of pressure: overpressure, relative
Pressure connection: 1/4" NPT external thread
Electrical connection: conduit
Protection class: IP44
Housing material: Painted carbon steel and transparent plastic front cover
Media temp.: 0...66C
Ambient temperature: 0...66C
Switch function/capacity: Modulating: 140 Ohm potentimeter
Mounting position: vertical
Brass bellows
Use with steam, air, noncombustible gases, or other fluids noncorrosive to the brass or phos-bronze (20 Bar / 300 psi models) bellows
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)
Do NOT use with combustible mediums or any medium chemically harmful to phos-bronze bellows (0.6-20 Bar / 10-300 psi models) or brass bellows (all other pressure range models)

Single potentiometer 140 Ohms. With optional surface mount through back of case.
Pressure adjustment range: 0...2068kPa
Differential pressure adjustment range: 85...330kPa
Max. pressure: 2241kPa


LG1093AA24/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Flame Sensor with 3/4 inch internal NPT mounting and Teflon shielded cable with 1" external conduit thread. Viewing window rated for 10bar (150psi).
Model: Cable length 16ft (4.9m)
Supply voltage: no
Temperature range: -40...176C
Maximum humidity: no
Approvals: FM


LG1093AA26/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Flame Sensor with 3/4 inch internal NPT mounting and Teflon shielded cable with 1" external conduit thread. Viewing window rated for 10bar (150psi).
Model: Cable length 61ft (12.8m)
Supply voltage: no
Temperature range: -40...176C
Maximum humidity: no
Approvals: FM


LG1093AA34/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Flame Sensor with 3/4 inch internal NPT mounting and Teflon shielded cable with 1" external conduit thread. Viewing window rated for 10bar (150psi).
Model: Cable length 16ft (4.9m)
Supply voltage: no
Temperature range: -40...176C
Maximum humidity: no
Approvals: CE/ATEX (EEx d IIA T3)


LG1093AA36/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Flame Sensor with 3/4 inch internal NPT mounting and Teflon shielded cable with 1" external conduit thread. Viewing window rated for 10bar (150psi).
Model: Cable length 61ft (12.8m)
Supply voltage: no
Temperature range: -40...176C
Maximum humidity: no
Approvals: CE/ATEX (EEx d IIA T3)


LG1093AA44/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Flame Sensor with 3/4 inch internal NPT mounting and Teflon shielded cable with 1" external conduit thread. Viewing window rated for 10bar (150psi).
Model: Cable length 16ft (4.9m)
Supply voltage: no
Temperature range: -40...176C
Maximum humidity: no
Approvals: CE/ATEX (EEx d IIC T3)


LG1093AA46/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Flame Sensor with 3/4 inch internal NPT mounting and Teflon shielded cable with 1" external conduit thread. Viewing window rated for 10bar (150psi).
Model: Cable length 61ft (12.8m)
Supply voltage: no
Temperature range: -40...176C
Maximum humidity: no
Approvals: CE/ATEX (EEx d IIC T3)


LG1093AC01/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Flame Sensor with 1.73" O.D. by 0.14" wide flange and 2-conductor armoured cable. Viewing window rated 428mbar (6.3psi)
Model: Cable length 9ft (2.7m)
Supply voltage: no
Temperature range: -40...176C
Maximum humidity: no
Approvals: CE/ATEX (EEx d IIA T3)


LG1093AC05/U

Honeywell Gas Turbine flame monitoring systems

The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
Gas Turbines for power genaration and compressors
Hardware outputs: For EG1033 amplifier modules only
EG1033AA: Transistor open collector
EG1033AB and EG1033AC: Relay contacts (SPDT)
Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
Flame Loss Response Time: 0.2 sec max.
Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
Operating distances up to 330m (1000ft), sensor to amplifier.
Qualified component on General Electric turbines.
Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
Note: LG1093 series UV sensors may not work as expected in DLE gas turbine applications (Dry Low-NOx). These use pre-selected LG1093 UV sensors which are not available through the regular Honeywell sales channels.
ALWAYS ask the manufacturer of the gas turbine for advice in case of an LG1093 service replacement on a DLN gas turbine application.

Flame Sensor with 1.73" O.D. by 0.14" wide flange and 2-conductor armoured cable. Viewing window rated 428mbar (6.3psi)
Model: Cable length 24ft (7.3m)
Supply voltage: no
Temperature range: -40...176C
Maximum humidity: no
Approvals: CE/ATEX (EEx d IIA T3)


LTA55XBE

Honeywell Industrial flame monitoring - Viewing Heads
Parts and accessories: Electrical

Liquid tight viewing head cable adapter for S55xBE series viewing heads. 1/2" NPTF conduit connection



LTA5XX

Honeywell Industrial flame monitoring - Viewing Heads
Parts and accessories: Electrical

Liquid tight viewing head cable adapter for old type S5XX series viewing heads only. 1/2" NPTF conduit connection



M-701-1

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

Swivel mount, 2" pipe slip to 1" NPT female connection. Anodized aluminium.



M-701-2

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

Swivel mount, 2" NPT female to 1" NPT female connection. Anodized aluminium.



M-701-2-FLG

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

Flanged swivel mount, 2" flanged to 1" NPTF



M-701-2-SS

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

Swivel mount, 2" NPT female to 1" NPT female. Stainless steel construction



M-701-3

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

Flanged swivel mount, 3-bolt, 4.5" flanged to 1" NPTF



M-701-3P

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

Swivel mount, 3" NPTF to 1" NPTF connection



M-701-4

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

Swivel mount, 2-bolt to 1" NPTF connection



M-701-5

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

Swivel mount bushing 1" x 1/2" NPT, 1/2" connection



M-702-6

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - various parts

Orifice and retaining ring set. Used for all viewing heads



MAXON-SMARTLINK-DS

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Actuators(90 span)
Product description: Actuator 33 or 101 Nm


ML7999A2001/U

Honeywell ControLinks - Electronic Fuel-Air Ratio Control System

ControLinks represents a value-added replacement of a mechanical parallel positioning fuel/air ratio control system by cam and linkage assembly controlling. For use with ML7999A2001 direct coupled actuators only, in Commercial or Industrial burners.
Commercial and small and medium sized industrial fuel/air controlled modulating gas, oil and dual fuel burners.
Approvals: CE, CSA, UL, FM, EAC
ONLY for use in "non-GAR" applications
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Works with the ML7999A2001 serial number controlled fail-safe direct coupled actuators.
Can store 2 fully independent fuel/air curves, that are electrically selectable
Can connect up to 4 actuators, 1 for air, 2 for fuels and 1 for flue gas recirculation. Minimal 2 actuators are needed to operate the system.
Note: ControLinks can operate fully independent from the used burner controller. However using the Honeywell 7800-series gets the most out of the system, by extended status and fault indication via the MicrosoftTM WindowsTM CE based full colour system display S7999D.

Special fail-safe actuator for ControLinks
Protection class: IP50
Supply voltage: 85..264 Vac
Power consumption: 15W
Angle of rotation: 90o
Runtime: 30s
Torque: 11.3Nm


MS051001

Honeywell Solenoid gas valve, normally closed VE4000A3
Electrical connection

CPI Switch for VE4100A



MS052501

Honeywell Solenoid gas valve, normally closed VE4000A1
CPI Switch for VE-series valves with bottom plug (1/4")

CPI Switch for VExxxxA/B/C/S DN20-25



MS054001

Honeywell Solenoid gas valve, normally closed VE4000A1
CPI Switch for VE-series valves with bottom plug (1/4")

CPI Switch for VExxxxA/B/C and VG4xxx DN32-40



MS055001

Honeywell Solenoid gas valve, normally closed VE4000A1
CPI Switch for VE-series valves with bottom plug (1/4")

CPI Switch for VExxxxA/B/C and VG4xxx DN50



MS056501

Honeywell Solenoid gas valve, normally closed VE4000A1
CPI Switch for VE-series valves with bottom plug (1/4")

CPI Switch for VExxxxA1 and VG4xxx DN65-80



MS058001

Honeywell Solenoid gas valve, normally closed VE4000A3
CPI Switch for VE-series valves with bottom plug (1/4")

CPI Switch for VE4065/80



Manual

Honeywell Intelligent safety combination shutoff gas valve with integrated smart technology

The "Vulcan" SV2 Series servo regulated combination valves are used for control and regulation of gaseous fuels in gas fired power burners, atmospheric gas boilers, melting furnaces, incinerators and other gas consuming appliances. These smart combination valves are available in various configurations from 3/4" up to 3". the following different versions:
Designed for but not limited to commercial burner and boiler applications
Gas valve type: Class A safety shut-off valves
Port connection: flanges
Media: Natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE, UL, CSA
Note: Contact a Honeywell Thermal Solutions Representative for more information.
Supply voltage: 24/120/230 Vac

Downloads
Comment: User Manual


NEMA-4X-ADD

Honeywell Heavy duty gas pilot ignitors
Accessories

NEMA 4X enclosure for igniter powerpack.



P222

Honeywell Flare monitoring system

Watchdog III is a flare stack monitoring system, guarding against the venting of hazardous gases in the atmosphere.
Can be used for continuous onsite flare monitoring
The fail-safe and well proven UVtron technology is used for flame detection.
Totally immune to sunlight:
Can be installed anywhere in a 360 degree radius around the flare stack. Operates in the 210 nm range of the spectrum (UV)
The viewing head can be mounted outside a explosion hazardous location:
The WATCHDOG viewing head can detect a flare more than 300 m away.
The signal processing unit can be mounted inside a nearby wiring cabinet.
Temperature range: -40...80C
Bus system description: Serial communication: RS422/485 (differential
4800, 9600, 19200 or 38400 baud (selectable)
Hardware outputs: Early indication: 2 x SPDT
Delayed indication: 1 x SPDT
0..20 mA or 4..20 mA (selectable)
Note: Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)

Individual components (excl. connector and cable)
Product description: Watchdog Signal Processor only with mounting base and terminal. Excl. connector.
Supply voltage: 85..264 Vac


P522AC

Honeywell Signal processors, selectable dual channel, P522

Selectable dual channel input for S55xBE viewing heads.
Battery backup 24V DC
Temperature range: 0...50C
R.H. range: 50...80%rh
Bus system description: RS422 (differential)
Hardware outputs: Flame relay: 2 x SPDT
Self-check relay: 1 x SPST
Alarm relay: 1 x SPST
0..20 mA or 4..20 mA (selectable)

With LED-indication
Power supply: 85..264 24 V AC


P522DC

Honeywell Signal processors, selectable dual channel, P522

Selectable dual channel input for S55xBE viewing heads.
Battery backup 24V DC
Temperature range: 0...50C
R.H. range: 50...80%rh
Bus system description: RS422 (differential)
Hardware outputs: Flame relay: 2 x SPDT
Self-check relay: 1 x SPST
Alarm relay: 1 x SPST
0..20 mA or 4..20 mA (selectable)

With LED-indication
Power supply: 24 V DC


P531AC

Honeywell Signal processors, independent dual channel, P531, P532

Independent dual channel input for viewing heads: S55xBx (channel 1 and 2) or S700/S800 (channel 3).
Battery backup 24V DC
Temperature range: -40...60C
R.H. range: 50...80%rh
Bus system description: Modbus
RS422 (differential)
Hardware outputs: Flame relay: 3 x DPDT
Self-check relay: 1 x SPDT
Alarm relay: 1 x SPST
0..20 mA or 4..20 mA (selectable)

With LED-indication
Power supply: 85..264 24 V AC


P531DC

Honeywell Signal processors, independent dual channel, P531, P532

Independent dual channel input for viewing heads: S55xBx (channel 1 and 2) or S700/S800 (channel 3).
Battery backup 24V DC
Temperature range: -40...60C
R.H. range: 50...80%rh
Bus system description: Modbus
RS422 (differential)
Hardware outputs: Flame relay: 3 x DPDT
Self-check relay: 1 x SPDT
Alarm relay: 1 x SPST
0..20 mA or 4..20 mA (selectable)

With LED-indication
Power supply: 24 V DC


P532AC

Honeywell Signal processors, independent dual channel, P531, P532

Independent dual channel input for viewing heads: S55xBx (channel 1 and 2) or S700/S800 (channel 3).
Battery backup 24V DC
Temperature range: -40...60C
R.H. range: 50...80%rh
Bus system description: Modbus
RS422 (differential)
Hardware outputs: Flame relay: 3 x DPDT
Self-check relay: 1 x SPDT
Alarm relay: 1 x SPST
0..20 mA or 4..20 mA (selectable)

With user interface integrated
Power supply: 85..264 24 V AC


P532DC

Honeywell Signal processors, independent dual channel, P531, P532

Independent dual channel input for viewing heads: S55xBx (channel 1 and 2) or S700/S800 (channel 3).
Battery backup 24V DC
Temperature range: -40...60C
R.H. range: 50...80%rh
Bus system description: Modbus
RS422 (differential)
Hardware outputs: Flame relay: 3 x DPDT
Self-check relay: 1 x SPDT
Alarm relay: 1 x SPST
0..20 mA or 4..20 mA (selectable)

With user interface integrated
Power supply: 24 V DC


POWERPACK-12-CS

Honeywell Heavy duty gas pilot ignitors
Accessories

12 Joule Power Pack, 120/230Vac, 50/60Hz



PT-GA1

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - various parts

High temperature gasket for 1" locking coupler



PT-QL1

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - various parts

Quartz lens for 1" locking coupler



Q7800A1005/U

Honeywell Burner Controls EC/RM7800-series
Wiring bases

Mounting subbase for 7800-series. Panel mount.



Q7800B1003/U

Honeywell Burner Controls EC/RM7800-series
Wiring bases

Mounting subbase for 7800-series. Wall mount.



Q7999A1006/U

Honeywell ControLinks - Electronic Fuel-Air Ratio Control System

ControLinks represents a value-added replacement of a mechanical parallel positioning fuel/air ratio control system by cam and linkage assembly controlling. For use with ML7999A2001 direct coupled actuators only, in Commercial or Industrial burners.
Commercial and small and medium sized industrial fuel/air controlled modulating gas, oil and dual fuel burners.
Approvals: CE, CSA, UL, FM, EAC
ONLY for use in "non-GAR" applications
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Works with the ML7999A2001 serial number controlled fail-safe direct coupled actuators.
Can store 2 fully independent fuel/air curves, that are electrically selectable
Can connect up to 4 actuators, 1 for air, 2 for fuels and 1 for flue gas recirculation. Minimal 2 actuators are needed to operate the system.
Note: ControLinks can operate fully independent from the used burner controller. However using the Honeywell 7800-series gets the most out of the system, by extended status and fault indication via the MicrosoftTM WindowsTM CE based full colour system display S7999D.

Mounting and wiring base
Protection class: IP40
Supply voltage: no
Power consumption: no
Angle of rotation: no
Runtime: no
Torque: no


R-518-09

Honeywell Industrial flame monitoring - Viewing Heads
Parts and accessories: Electrical

Quick disconnect connector only for all S55xBE viewing head models



R-518-10

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - cable connector for U2-S

Quick disconnect 12-pins Turck connector for U2-S "non-PF" models.



R-518-12

Honeywell Industrial flame monitoring - Viewing Heads
Parts and accessories: Mounting

1" NPT Ultem heat and electrical insulating nipple for S55xB/BE series viewing heads swivel mount.



R-518-13

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads
Parts and accessories: Mounting

1/2 in. NPT Ultem heat insulating nipple for S700/S800 series viewing heads



R-518-CL12-HTG

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1" NPT locking coupler with high temperature gasket



R-518-CL12-PG

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1" NPT aluminum locking quick disconnect/cam and groove coupler adapter with 1/2" NPT purge port. Used with U2 processor/viewing heads



R-518-CL13-HTG

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1/2" NPT locking coupler with high temperature gasket



R-518-PT12

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1" NPT Ultem insulating locking coupler adapter. Used with U2 processor/viewing head



R-518-PT12L

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1" NPT Ultem locking coupler adapter with quartz lens



R-518-PT13

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1/2" NPT Ultem locking coupler adapter only



R-518-PT13L

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - pipe fitting accessories

1/2" NPT Ultem locking coupler adapter with quartz lens



R4343D1009

Honeywell Flame relay R4343

The R4343D/E series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations. light.
Flame current meter jack socket on the front permits monitoring of flame signal strength, by using any appropriate microampere meter (0-10uA minimum scale).
Plug-in mounts onto a sub base (included) for surface mounting.
Providing an indication of absense or presence of a flame in intermittent industrial oil/gas burner applications by an open or closed relay contact.
Approvals: CE approved according EN298 (for intermittent operation)
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
R4343D models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
R4343E models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: SPARE PART ONLY The R4343-series flame switches no longer meet the approval requirements under the GAR, LVD and EMCD and cannot be used for new installations in Europe.
Outputs: 1xDPDT
Operation: Intermit.

Ionisation flame detectors
Flame failure response time: <1s
Flame detector: Rectification
Supply voltage: 110..120 Vac


R4343D1017

Honeywell Flame relay R4343

The R4343D/E series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations. light.
Flame current meter jack socket on the front permits monitoring of flame signal strength, by using any appropriate microampere meter (0-10uA minimum scale).
Plug-in mounts onto a sub base (included) for surface mounting.
Providing an indication of absense or presence of a flame in intermittent industrial oil/gas burner applications by an open or closed relay contact.
Approvals: CE approved according EN298 (for intermittent operation)
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
R4343D models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
R4343E models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: SPARE PART ONLY The R4343-series flame switches no longer meet the approval requirements under the GAR, LVD and EMCD and cannot be used for new installations in Europe.
Outputs: 1xDPDT
Operation: Intermit.

Ionisation flame detectors
Flame failure response time: <1s
Flame detector: Rectification
Supply voltage: 220..240 Vac


R4343D1041-ST005

Honeywell Flame relay R4343

The R4343D/E series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations. light.
Flame current meter jack socket on the front permits monitoring of flame signal strength, by using any appropriate microampere meter (0-10uA minimum scale).
Plug-in mounts onto a sub base (included) for surface mounting.
Providing an indication of absense or presence of a flame in intermittent industrial oil/gas burner applications by an open or closed relay contact.
Approvals: CE approved according EN298 (for intermittent operation)
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
R4343D models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
R4343E models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: SPARE PART ONLY The R4343-series flame switches no longer meet the approval requirements under the GAR, LVD and EMCD and cannot be used for new installations in Europe.
Outputs: 1xDPDT
Operation: Intermit.

Ionisation flame detectors
Flame failure response time: <2s
Flame detector: Rectification
Supply voltage: 115/230 Vac


R4343E1006

Honeywell Flame relay R4343

The R4343D/E series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations. light.
Flame current meter jack socket on the front permits monitoring of flame signal strength, by using any appropriate microampere meter (0-10uA minimum scale).
Plug-in mounts onto a sub base (included) for surface mounting.
Providing an indication of absense or presence of a flame in intermittent industrial oil/gas burner applications by an open or closed relay contact.
Approvals: CE approved according EN298 (for intermittent operation)
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
R4343D models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
R4343E models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: SPARE PART ONLY The R4343-series flame switches no longer meet the approval requirements under the GAR, LVD and EMCD and cannot be used for new installations in Europe.
Outputs: 1xDPDT
Operation: Intermit.

UV flame detectors
Flame failure response time: <1s
Flame detector: UV
Supply voltage: 110..120 Vac


R4343E1014

Honeywell Flame relay R4343

The R4343D/E series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations. light.
Flame current meter jack socket on the front permits monitoring of flame signal strength, by using any appropriate microampere meter (0-10uA minimum scale).
Plug-in mounts onto a sub base (included) for surface mounting.
Providing an indication of absense or presence of a flame in intermittent industrial oil/gas burner applications by an open or closed relay contact.
Approvals: CE approved according EN298 (for intermittent operation)
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
R4343D models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
R4343E models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: SPARE PART ONLY The R4343-series flame switches no longer meet the approval requirements under the GAR, LVD and EMCD and cannot be used for new installations in Europe.
Outputs: 1xDPDT
Operation: Intermit.

UV flame detectors
Flame failure response time: <1s
Flame detector: UV
Supply voltage: 220..240 Vac


R4343E1048-ST005

Honeywell Flame relay R4343

The R4343D/E series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations. light.
Flame current meter jack socket on the front permits monitoring of flame signal strength, by using any appropriate microampere meter (0-10uA minimum scale).
Plug-in mounts onto a sub base (included) for surface mounting.
Providing an indication of absense or presence of a flame in intermittent industrial oil/gas burner applications by an open or closed relay contact.
Approvals: CE approved according EN298 (for intermittent operation)
Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh
R4343D models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
R4343E models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
Note: SPARE PART ONLY The R4343-series flame switches no longer meet the approval requirements under the GAR, LVD and EMCD and cannot be used for new installations in Europe.
Outputs: 1xDPDT
Operation: Intermit.

UV flame detectors
Flame failure response time: <2s
Flame detector: UV
Supply voltage: 115/230 Vac


R7824C1002/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

Used with RM7824A 24VDC model only. For UV sensor C7024E/F. Self-Check. Not CE approved. FFRT: 3.0s



R7847A1025/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For flame rod (cable<5m). FFRT: EU=1.0s / US=0.8s R7847A activates 24h autorecycle timer when used in CE approved EC/RM78xx relay modules.



R7847A1033/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For flame rod (cable<5m). FFRT: EU=2.0s / US=3.0s R7847A activates 24h autorecycle timer when used in CE approved EC/RM78xx relay modules.



R7847A1074/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For flame rod (cable>5m) and UV sensor C7012A/C/G. FFRT: EU=1.0s / US=0.8s R7847A activates 24h autorecycle timer when used in CE approved EC/RM78xx relay modules.



R7847A1082/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For flame rod (cable>5m) and UV sensor C7012A/C/G. FFRT: EU=2.0s / US=3.0s R7847A activates 24h autorecycle timer when used in CE approved EC/RM78xx relay modules.



R7847B1023/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For flame rod (cable<5m). Ampli-Check. FFRT: EU=1.0s / US=0.8s



R7847B1031/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For flame rod (cable<5m). Ampli-Check. FFRT: EU=2.0s / US=3.0s



R7847B1064/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For flame rod (cable>5m) and UV sensor C7012A/C/G. Ampli-Check. FFRT: EU=1.0s / US=0.8s



R7847B1072/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For flame rod (cable>5m) and UV sensor C7012A/C/G. Ampli-Check. FFRT: EU=2.0s / US=3.0s



R7847C1005/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For C7012E/F UV sensor. Shutter-Check. Not CE approved. FFRT: EU=2.0s / US=3.0s



R7849A1015/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For UV sensors C7027/35/44. FFRT: EU=1.0s / US=0.8s R7849A activates 24h autorecycle timer when used in CE approved EC/RM78xx relay modules.



R7849A1023/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For UV sensors C7027/35/44. FFRT: EU=2.0s / US=3.0s R7849A activates 24h autorecycle timer when used in CE approved EC/RM78xx relay modules.



R7849B1013/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For UV sensors C7027/35/44. Ampli-Check. FFRT: EU=1.0s / US=0.8s NOT CE APPROVED



R7849B1021/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For UV sensors C7027/35/44. Ampli-Check. FFRT: EU=2.0s / US=3.0s NOT CE APPROVED



R7851B1000/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For UV sensors C7927 and visible light C7962. Ampli-Check. FFRT: EU=2.0s / US=3.0s NOT CE APPROVED



R7851C1008/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For UV sensors C7961E/F. Shutter-Check. FFRT: EU=2.0s / US=3.0s



R7852B1009/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For IR sensors C7915. Ampli-Check. FFRT: EU=2.0s / US=3.0s



R7861A1026/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For UV sensors C7061A/F. Shutter-Check. FFRT: EU=2.0s / US=3.0s



R7861A1034/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For UV sensors C7061A/F. Shutter-Check. FFRT: EU=1.0s / US=0.8s



R7886A1001/U

Honeywell Burner Controls EC/RM7800-series
Flame amplifiers

For UV sensors C7076A/D/F. Shutter-Check. FFRT: EU=2.0s / US=3.0s



R7999A1005/U

Honeywell ControLinks - Electronic Fuel-Air Ratio Control System

ControLinks represents a value-added replacement of a mechanical parallel positioning fuel/air ratio control system by cam and linkage assembly controlling. For use with ML7999A2001 direct coupled actuators only, in Commercial or Industrial burners.
Commercial and small and medium sized industrial fuel/air controlled modulating gas, oil and dual fuel burners.
Approvals: CE, CSA, UL, FM, EAC
ONLY for use in "non-GAR" applications
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Works with the ML7999A2001 serial number controlled fail-safe direct coupled actuators.
Can store 2 fully independent fuel/air curves, that are electrically selectable
Can connect up to 4 actuators, 1 for air, 2 for fuels and 1 for flue gas recirculation. Minimal 2 actuators are needed to operate the system.
Note: ControLinks can operate fully independent from the used burner controller. However using the Honeywell 7800-series gets the most out of the system, by extended status and fault indication via the MicrosoftTM WindowsTM CE based full colour system display S7999D.

Controller
Protection class: IP40
Supply voltage: 110..120 Vac
Power consumption: 10W
Angle of rotation: no
Runtime: no
Torque: no


R7999B1003/U

Honeywell ControLinks - Electronic Fuel-Air Ratio Control System

ControLinks represents a value-added replacement of a mechanical parallel positioning fuel/air ratio control system by cam and linkage assembly controlling. For use with ML7999A2001 direct coupled actuators only, in Commercial or Industrial burners.
Commercial and small and medium sized industrial fuel/air controlled modulating gas, oil and dual fuel burners.
Approvals: CE, CSA, UL, FM, EAC
ONLY for use in "non-GAR" applications
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Works with the ML7999A2001 serial number controlled fail-safe direct coupled actuators.
Can store 2 fully independent fuel/air curves, that are electrically selectable
Can connect up to 4 actuators, 1 for air, 2 for fuels and 1 for flue gas recirculation. Minimal 2 actuators are needed to operate the system.
Note: ControLinks can operate fully independent from the used burner controller. However using the Honeywell 7800-series gets the most out of the system, by extended status and fault indication via the MicrosoftTM WindowsTM CE based full colour system display S7999D.

Controller
Protection class: IP40
Supply voltage: 220..240 Vac
Power consumption: 10W
Angle of rotation: no
Runtime: no
Torque: no


R8001A1001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Configurable Safety Modules
Product description: Base Module


R8001B2001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Configurable Safety Modules
Product description: Burner Control Module
Comment: Needs sub base


R8001C6001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Configurable Safety Modules
Product description: Fuel Air Ratio Module
Comment: Needs sub base


R8001D4001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Programmable Logic Modules
Product description: Digital I/O Module
Comment: Needs sub base


R8001F1041/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Flame Amplifier Modules
Product description: IR Ampli-Check Flame Amplifier Module
Comment: Needs sub base


R8001F1091/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Flame Amplifier Modules
Product description: UV/Visible Light Ampli-Check Flame Amplifier Module
Comment: Needs sub base


R8001K1010/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Accessories
Product description: Web based Colour Touchscreen Display 10"


R8001K5001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Accessories
Product description: Web based Colour Touchscreen Display 7"


R8001L8001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Configurable Safety Modules
Product description: Limit Control Module
Comment: Needs sub base


R8001M1050

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Actuators(90 span)
Product description: Actuator, 450 steps, 30s runtime, 5.5 Nm, IP40


R8001M1150

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Actuators(90 span)
Product description: Actuator, 450 steps, 30s runtime, 17 Nm, IP40


R8001M4050

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Actuators(90 span)
Product description: Actuator 900 steps, 15s runtime, 5.5 Nm, IP66


R8001M4150

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Actuators(90 span)
Product description: Actuator 900 steps, 15s runtime, 17 Nm, IP66


R8001N7001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Programmable Logic Modules
Product description: Annunciator Module
Comment: Needs sub base


R8001S1051/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Flame Amplifier Modules
Product description: UV Shutter-Check Flame Amplifier Module
Comment: Needs sub base


R8001S1071/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Flame Amplifier Modules
Product description: UV Ampli-Check Flame Amplifier Module
Comment: Needs sub base


R8001S9001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Accessories
Product description: DIN rail Mounting Sub-base
Comment: One per module needed!


R8001U3001/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Programmable Logic Modules
Product description: Analogue I/O Module
Comment: Needs sub base


R8001V1031/U

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE Flame Amplifier Modules
Product description: Rectification Ampli-Check Flame Amplifier Module
Comment: Needs sub base


RM7823A1016/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

Flame switch only (no program sequence). 120Vac models.
Control model: Flame switch
Outputs: 2xSPDT
Operation: Cont.
Pilot: no
Prepurge timer: no
Pilot ignition time: no
Main ignition time: no
Post purge time: no
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


RM7824A1006/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 24VDC (RM7824)
Control model: Primary
Outputs: no
Operation: Cont.
Pilot: no
Prepurge timer: no
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: no
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no
Comment: C7024E/F UV detector only


RM7840E1016/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 120Vac (RM78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Interrupted
Prepurge timer: yes
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: 15s
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


RM7840G1014/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 120Vac (RM78xx)
Control model: Atmosferic
Outputs: LF/Modulate
Operation: Cont.
Pilot: Interrupted
Prepurge timer: yes
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: 15s
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


RM7840L1018/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 120Vac (RM78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Interrupted
Prepurge timer: yes
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: 15s
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


RM7840L1026/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 120Vac (RM78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: 15s
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


RM7840L1075/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 120Vac (RM78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Interrupted
Prepurge timer: yes
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: 15s
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: Integrated
Comment: Uses S7800A1142/U display for programming


RM7840M1017/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 120Vac (RM78xx)
Control model: Atmosferic
Outputs: on/off
Operation: Cont.
Pilot: Interrupted
Prepurge timer: no
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: 15s
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


RM7850A1001/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 120Vac (RM78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 3/5s
Main ignition time: 3/5s
Post purge time: 2s
Number of ignition attempts: 1
Flame failure response time: 1,0/2,0s
Valve proofing system: no


RM7850A1019/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 120Vac (RM78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 3/5s
Main ignition time: 3/5s
Post purge time: 15s
Number of ignition attempts: 1
Flame failure response time: 1,0/2,0s
Valve proofing system: no


RM7850A1027/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 120Vac (RM78xx)
Control model: Full
Outputs: HF/LF/Modulate
Operation: Cont.
Pilot: Selectable
Prepurge timer: yes
Pilot ignition time: 3/5s
Main ignition time: 3/5s
Post purge time: 30s
Number of ignition attempts: 1
Flame failure response time: 1,0/2,0s
Valve proofing system: no


RM7890A1015/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 120Vac (RM78xx)
Control model: Primary
Outputs: no
Operation: Intermit.
Pilot: Intermittent
Prepurge timer: no
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: no
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no
Comment: No shutter check


RM7890B1014/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 120Vac (RM78xx)
Control model: Primary
Outputs: no
Operation: Cont.
Pilot: Intermittent
Prepurge timer: no
Pilot ignition time: 4/10s
Main ignition time: no
Post purge time: no
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no


RM7890B1030/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

American models 120Vac (RM78xx)
Control model: Primary
Outputs: no
Operation: Cont.
Pilot: Intermittent
Prepurge timer: no
Pilot ignition time: no
Main ignition time: no
Post purge time: no
Number of ignition attempts: no
Flame failure response time: 0,8/3,0s
Valve proofing system: no
Comment: Fixed 4s safety time.


RM7890B1055/U

Honeywell Burner Controls EC/RM7800-series

The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution.
For all type of burners with unlimited capacity.
Approvals: CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
CE approved according EN298 for continuous operation (when used with correct flame amplifier and flame sensor). EU models only.
SIL-3 Capable certified. All models, except EC/RM7823 flame switches.
APAVE accepted. EU models only.
CSA/UL approved. US models only.
Protection class: Europe: IP00 (cabinet mount only)
Americas: NEMA 1 (cabinet or wall mount)
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Modular design with plug-in modules. Selectable pre-purge time by ST7800A1xxx/U module selection.
Accepts all existing Honeywell optical flame detectors and flame rods.
All information regarding the burner control (6 last lockout conditions, flame signal, hours of operation ...) are available on the keyboard display module or through communication.
Note: About Flame Failure Response Times (FFRT):
European 7800-series burner controllers (EU): 1.0 or 2.0s (depends on flame amplifier model).
American 7800-series burner controllers (US): 0.8 or 3.0s (depends on flame amplifier model).
Flame detector: Depends on plug-in amplifier

European models 120Vac (RM78xx)
Control model: Primary
Outputs: on/off
Operation: Cont.
Pilot: Intermittent
Prepurge timer: no
Pilot ignition time: 5/10s
Main ignition time: no
Post purge time: no
Number of ignition attempts: selectable
Flame failure response time: 1,0/2,0s
Valve proofing system: no


S256BE

Honeywell Flare monitoring system

Watchdog III is a flare stack monitoring system, guarding against the venting of hazardous gases in the atmosphere.
Can be used for continuous onsite flare monitoring
The fail-safe and well proven UVtron technology is used for flame detection.
Totally immune to sunlight:
Can be installed anywhere in a 360 degree radius around the flare stack. Operates in the 210 nm range of the spectrum (UV)
The viewing head can be mounted outside a explosion hazardous location:
The WATCHDOG viewing head can detect a flare more than 300 m away.
The signal processing unit can be mounted inside a nearby wiring cabinet.
Temperature range: -40...80C
Bus system description: Serial communication: RS422/485 (differential
4800, 9600, 19200 or 38400 baud (selectable)
Hardware outputs: Early indication: 2 x SPDT
Delayed indication: 1 x SPDT
0..20 mA or 4..20 mA (selectable)
Note: Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)

Individual components (excl. connector and cable)
Product description: Watchdog UV Digital flare stack pilot monitor viewing head. Powered by P222.
Supply voltage: 24 Vdc


S550BE

Honeywell Industrial flame monitoring - Viewing Heads

The S55xBE viewing head delivers flame discrimination in the toughest environments and is capable to detect the flame of almost every available fuel type or fuel mixture. With automatic setup, three channels and the ability to monitor UV and IR flame components simultaneously or separately, the P532 signal processor offers improved burner up time and reliability.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: GOST, FM, UL, CSA & NRTL/C Approved
IECEx certification for specific models (global)
ATEX certification for S550BE-EX (3rd party product)
Protection class: NEMA 4x, IP64
S55xBE: Zone 2 Class 1 Div 2 Group A, B, C and D
S55xBE: IECEX Cat 3 (Zone 2) II 3G IIC T5
S550BE-EX: ATEX {EX} II 2 G Ex d IIC T6 for use in Zone 1 and 2 (3rd party product)
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Sensor: UV Tube, Solid State IR sensor or both UV+IR
Response UV: 210 nm Peak / IR: 1400 nm Peak
Technology: Pulse Count (UV) and Flicker (IR)
Self-check: Electronic (no mechanical moving parts)
Works in combination with P531, P532 and P522 signal processors (P522 with red button labels only).
Note: All S55xBE / P5xx series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S55xBE viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S55xBE viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads S55xBE
Product description: Dual UV/IR viewing head, with Turck connector (included)
Flame detector: UVTron+IR
Comment: Dual LED display for flame signal


S550BE-EX

Honeywell Industrial flame monitoring - Viewing Heads

The S55xBE viewing head delivers flame discrimination in the toughest environments and is capable to detect the flame of almost every available fuel type or fuel mixture. With automatic setup, three channels and the ability to monitor UV and IR flame components simultaneously or separately, the P532 signal processor offers improved burner up time and reliability.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: GOST, FM, UL, CSA & NRTL/C Approved
IECEx certification for specific models (global)
ATEX certification for S550BE-EX (3rd party product)
Protection class: NEMA 4x, IP64
S55xBE: Zone 2 Class 1 Div 2 Group A, B, C and D
S55xBE: IECEX Cat 3 (Zone 2) II 3G IIC T5
S550BE-EX: ATEX {EX} II 2 G Ex d IIC T6 for use in Zone 1 and 2 (3rd party product)
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Sensor: UV Tube, Solid State IR sensor or both UV+IR
Response UV: 210 nm Peak / IR: 1400 nm Peak
Technology: Pulse Count (UV) and Flicker (IR)
Self-check: Electronic (no mechanical moving parts)
Works in combination with P531, P532 and P522 signal processors (P522 with red button labels only).
Note: All S55xBE / P5xx series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S55xBE viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S55xBE viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads S55xBE-EX (Explosion proof). 3rd party product.
Product description: Dual UV/IR viewing head with exlosion proof enclosure. Available via distributor only
Flame detector: UVTron+IR
Comment: ATEX (Ex d IIC T6) - Zone 1 & 2


S552BE

Honeywell Industrial flame monitoring - Viewing Heads

The S55xBE viewing head delivers flame discrimination in the toughest environments and is capable to detect the flame of almost every available fuel type or fuel mixture. With automatic setup, three channels and the ability to monitor UV and IR flame components simultaneously or separately, the P532 signal processor offers improved burner up time and reliability.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: GOST, FM, UL, CSA & NRTL/C Approved
IECEx certification for specific models (global)
ATEX certification for S550BE-EX (3rd party product)
Protection class: NEMA 4x, IP64
S55xBE: Zone 2 Class 1 Div 2 Group A, B, C and D
S55xBE: IECEX Cat 3 (Zone 2) II 3G IIC T5
S550BE-EX: ATEX {EX} II 2 G Ex d IIC T6 for use in Zone 1 and 2 (3rd party product)
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Sensor: UV Tube, Solid State IR sensor or both UV+IR
Response UV: 210 nm Peak / IR: 1400 nm Peak
Technology: Pulse Count (UV) and Flicker (IR)
Self-check: Electronic (no mechanical moving parts)
Works in combination with P531, P532 and P522 signal processors (P522 with red button labels only).
Note: All S55xBE / P5xx series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S55xBE viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S55xBE viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads S55xBE
Product description: Single IR viewing head, with Turck connector (included)
Flame detector: IR
Comment: Single LED display for flame signal


S556BE

Honeywell Industrial flame monitoring - Viewing Heads

The S55xBE viewing head delivers flame discrimination in the toughest environments and is capable to detect the flame of almost every available fuel type or fuel mixture. With automatic setup, three channels and the ability to monitor UV and IR flame components simultaneously or separately, the P532 signal processor offers improved burner up time and reliability.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: GOST, FM, UL, CSA & NRTL/C Approved
IECEx certification for specific models (global)
ATEX certification for S550BE-EX (3rd party product)
Protection class: NEMA 4x, IP64
S55xBE: Zone 2 Class 1 Div 2 Group A, B, C and D
S55xBE: IECEX Cat 3 (Zone 2) II 3G IIC T5
S550BE-EX: ATEX {EX} II 2 G Ex d IIC T6 for use in Zone 1 and 2 (3rd party product)
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Sensor: UV Tube, Solid State IR sensor or both UV+IR
Response UV: 210 nm Peak / IR: 1400 nm Peak
Technology: Pulse Count (UV) and Flicker (IR)
Self-check: Electronic (no mechanical moving parts)
Works in combination with P531, P532 and P522 signal processors (P522 with red button labels only).
Note: All S55xBE / P5xx series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S55xBE viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S55xBE viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads S55xBE
Product description: Single UV viewing head, with Turck connector (included)
Flame detector: UVTron
Comment: Single LED display for flame signal


S702

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads

The S700 and S800 viewing head is capable to detect the flame of almost every available fuel type or fuel mixture and have a high flame discrimination capabilty because of adjustable background radiation sensitivity.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: FM, CSA approved
SIL3 capable
Protection class: NEMA 4x, IP64
Ambient temperature: 0...50C
Maximum humidity: 85%rh
S702 and S802 models: Germanium photo diode with spectral response 1110 to 1660 nm
S706 and S806 models: UVton Tube with response 185 to 260 nm
Fali-safe: no mechanical shutter needed because of the use of electronic monitoring and digital signal processing.
Technology: Flicker (S702/S802 - IR) and Pulse Count (S706/S806 - UV)
Works in combination with 700DCSP, 700ACSP and 800SP and on the 3rd channel of the P531 and P532 signal processors.
Note: All S70x/80x/700/800 series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S706/S706 UV viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S706/S806 UV viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads , with cable connector. Incl. 4.5 m cable and connector.
Product description: Single IR viewing head.
Flame detector: IR


S702PF

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads

The S700 and S800 viewing head is capable to detect the flame of almost every available fuel type or fuel mixture and have a high flame discrimination capabilty because of adjustable background radiation sensitivity.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: FM, CSA approved
SIL3 capable
Protection class: NEMA 4x, IP64
Ambient temperature: 0...50C
Maximum humidity: 85%rh
S702 and S802 models: Germanium photo diode with spectral response 1110 to 1660 nm
S706 and S806 models: UVton Tube with response 185 to 260 nm
Fali-safe: no mechanical shutter needed because of the use of electronic monitoring and digital signal processing.
Technology: Flicker (S702/S802 - IR) and Pulse Count (S706/S806 - UV)
Works in combination with 700DCSP, 700ACSP and 800SP and on the 3rd channel of the P531 and P532 signal processors.
Note: All S70x/80x/700/800 series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S706/S706 UV viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S706/S806 UV viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads with 15 Ft (3.5 m) factory mounted over-moulded cable
Product description: Single IR viewing head.
Flame detector: IR


S706

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads

The S700 and S800 viewing head is capable to detect the flame of almost every available fuel type or fuel mixture and have a high flame discrimination capabilty because of adjustable background radiation sensitivity.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: FM, CSA approved
SIL3 capable
Protection class: NEMA 4x, IP64
Ambient temperature: 0...50C
Maximum humidity: 85%rh
S702 and S802 models: Germanium photo diode with spectral response 1110 to 1660 nm
S706 and S806 models: UVton Tube with response 185 to 260 nm
Fali-safe: no mechanical shutter needed because of the use of electronic monitoring and digital signal processing.
Technology: Flicker (S702/S802 - IR) and Pulse Count (S706/S806 - UV)
Works in combination with 700DCSP, 700ACSP and 800SP and on the 3rd channel of the P531 and P532 signal processors.
Note: All S70x/80x/700/800 series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S706/S706 UV viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S706/S806 UV viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads , with cable connector. Incl. 4.5 m cable and connector.
Product description: Single UV viewing head.
Flame detector: UV


S706PF

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads

The S700 and S800 viewing head is capable to detect the flame of almost every available fuel type or fuel mixture and have a high flame discrimination capabilty because of adjustable background radiation sensitivity.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: FM, CSA approved
SIL3 capable
Protection class: NEMA 4x, IP64
Ambient temperature: 0...50C
Maximum humidity: 85%rh
S702 and S802 models: Germanium photo diode with spectral response 1110 to 1660 nm
S706 and S806 models: UVton Tube with response 185 to 260 nm
Fali-safe: no mechanical shutter needed because of the use of electronic monitoring and digital signal processing.
Technology: Flicker (S702/S802 - IR) and Pulse Count (S706/S806 - UV)
Works in combination with 700DCSP, 700ACSP and 800SP and on the 3rd channel of the P531 and P532 signal processors.
Note: All S70x/80x/700/800 series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S706/S706 UV viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S706/S806 UV viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads with 15 Ft (3.5 m) factory mounted over-moulded cable
Product description: Single UV viewing head.
Flame detector: UV


S7800A1001/U

Honeywell Burner Controls EC/RM7800-series
Keyboard display modules

Language: English. With integrated Modbus communication option. Revision 5 model.



S7800A1035/U

Honeywell Burner Controls EC/RM7800-series
Keyboard display modules

Language: French. Revision 4 model.



S7800A1142/U

Honeywell Burner Controls EC/RM7800-series
Keyboard display modules

Language: English. Enhanced model, needed to program Enhanced 7800-series models (with VPS).



S7800A1167/U

Honeywell Burner Controls EC/RM7800-series
Keyboard display modules

Language: Spanish. Enhanced model, needed to program Enhanced 7800-series models (with VPS).



S7810A1009/U

Honeywell Burner Controls EC/RM7800-series
Remote Communication Modules

Data Controlbus Module for communication or for remote S7800 mounting.



S7810M1003/U

Honeywell Burner Controls EC/RM7800-series
Remote Communication Modules

MODBUS communication card. For US models only, not CE approved (includes remote reset over Modbus).



S7810M1029/U

Honeywell Burner Controls EC/RM7800-series
Remote Communication Modules

MODBUS communication card. CE approved (no remote reset over Modbus).



S7820A1007/U

Honeywell Burner Controls EC/RM7800-series
Remote Communication Modules

Remote Reset Module.



S7830A1005/U

Honeywell Burner Controls EC/RM7800-series
Expanded annunciator (NA only)

Expanded Annunciator to show additional information about faults in the limit string, only for use in Americas. Voltage: 120V, 50/60Hz. Uses Q7800 mounting base (not included).



S7999D1048/U

Honeywell ControLinks - Electronic Fuel-Air Ratio Control System

ControLinks represents a value-added replacement of a mechanical parallel positioning fuel/air ratio control system by cam and linkage assembly controlling. For use with ML7999A2001 direct coupled actuators only, in Commercial or Industrial burners.
Commercial and small and medium sized industrial fuel/air controlled modulating gas, oil and dual fuel burners.
Approvals: CE, CSA, UL, FM, EAC
ONLY for use in "non-GAR" applications
Ambient temperature: -40...60C
Maximum humidity: 85%rh
Works with the ML7999A2001 serial number controlled fail-safe direct coupled actuators.
Can store 2 fully independent fuel/air curves, that are electrically selectable
Can connect up to 4 actuators, 1 for air, 2 for fuels and 1 for flue gas recirculation. Minimal 2 actuators are needed to operate the system.
Note: ControLinks can operate fully independent from the used burner controller. However using the Honeywell 7800-series gets the most out of the system, by extended status and fault indication via the MicrosoftTM WindowsTM CE based full colour system display S7999D.

Colour touch, Windows CE based Configuration and Status display
Protection class: IP40
Supply voltage: 24 Vac
Power consumption: 12W
Angle of rotation: no
Runtime: no
Torque: no


S802

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads

The S700 and S800 viewing head is capable to detect the flame of almost every available fuel type or fuel mixture and have a high flame discrimination capabilty because of adjustable background radiation sensitivity.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: FM, CSA approved
SIL3 capable
Protection class: NEMA 4x, IP64
Ambient temperature: 0...50C
Maximum humidity: 85%rh
S702 and S802 models: Germanium photo diode with spectral response 1110 to 1660 nm
S706 and S806 models: UVton Tube with response 185 to 260 nm
Fali-safe: no mechanical shutter needed because of the use of electronic monitoring and digital signal processing.
Technology: Flicker (S702/S802 - IR) and Pulse Count (S706/S806 - UV)
Works in combination with 700DCSP, 700ACSP and 800SP and on the 3rd channel of the P531 and P532 signal processors.
Note: All S70x/80x/700/800 series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S706/S706 UV viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S706/S806 UV viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads , with cable connector. Incl. 4.5 m cable and connector.
Product description: Single IR viewing head, in stainless steel enclosure.
Flame detector: IR


S806

Honeywell Industrial flame monitoring - S700/S800 Viewing Heads

The S700 and S800 viewing head is capable to detect the flame of almost every available fuel type or fuel mixture and have a high flame discrimination capabilty because of adjustable background radiation sensitivity.
Industrial process burners, multiple burner systems, incinerators, ovens, kilns, etc.
Approvals: FM, CSA approved
SIL3 capable
Protection class: NEMA 4x, IP64
Ambient temperature: 0...50C
Maximum humidity: 85%rh
S702 and S802 models: Germanium photo diode with spectral response 1110 to 1660 nm
S706 and S806 models: UVton Tube with response 185 to 260 nm
Fali-safe: no mechanical shutter needed because of the use of electronic monitoring and digital signal processing.
Technology: Flicker (S702/S802 - IR) and Pulse Count (S706/S806 - UV)
Works in combination with 700DCSP, 700ACSP and 800SP and on the 3rd channel of the P531 and P532 signal processors.
Note: All S70x/80x/700/800 series Flame Safety Products are approved by FM Global for use in SIL 3 environment.
All S706/S706 UV viewing heads are immune to X-Rays and Gamma radiation, making them ideal for a broad variety of industrial applications.
Other than any other flame scanner, the S706/S806 UV viewing heads perform background pulse counting for tube health and therefore don't need a mechanical shutter system for self-checking.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Operation: Cont.

Flame scanner heads , with cable connector. Incl. 4.5 m cable and connector.
Product description: Single UV viewing head, in stainless steel enclosure
Flame detector: UV


SLATE-Spotlight

Honeywell Honeywell Thermal Solutions Product Catalogue

These pages show an overview and offer downloads of data sheets and certificates of the Honeywell branded Thermal Solutions products and solutions that are available for ordering through the Honeywell Europe sales channels, such as:
SLATETM burner/boiler management system
EC/RM7800-series "Blue Line" burner controllers
C7xxx-series optical flame sensors
IFM industrial flame monitoring products (former "IRIS Systems Inc.")
VE-series solenoid valves
C6097 gas pressure switches
and more...
Note: Kromschroeder is now part of Honeywell. An overview of and downloads for the Kromschroeder branded Thermal Solutions products can be found in Docuthek.
Please visit:: http://www.docuthek.com


Comment: Download SLATE brochure and promo video


SLATEAXTOOL

Honeywell SLATE(TM) Combustion Management System

With the revolutionary integration of configurable safety and programmable logic, SLATETM is easily customized for virtually any application in any industry, in less time, and with far less complexity.
The SLATETM Combustion Management System is prepared for remote monitoring using the Thermal IQ Honeywell Connected Plant solution.
Universal I/O scheme lets you choose how to use each module, and the customizable touchscreen display or PC web browser (optimized for ChromeTM) allows you to easily change the end user experience.
Burner management
Steam generation
Kilns and ovens
Commercial and industrial boilers
Make-up air
Process heating
Approvals: CE approved: EN298 for burner controllers in continuous operation, EN12067-2 for electronic fuel/air ratio controllers and EN1854 for automatic valve proofing systems
SIL 3 "capable" certification
CSA/UL/FM approved (US/CA)
Protection class: IP00 / NEMA 1 (cabinet mounting)
Ambient temperature: -10...60C
Maximum humidity: 90%rh
SLATETM Online configurator (global site): https://combustion.honeywell.com/slate/
the online configurator simplifies selection of modules and system design
One stop shop for downloading SLATE AX programming software, firmware upgrades and more
Pre-configuration files are available for download to emulate most commonly used burner controllers
Operation: Automatic
Valve proofing system: Integrated
Supply voltage: 24 Vdc / 24..264 Vac
Features: Easy installation, efficient operation and fast service because of:
DIN-rail mounting (modular platform)
On-board communications capabilities (Ethernet, Modbus RS485/TCP, BACnet)
Intuitive diagnostics (touch display, PC or smart phone via web browser)
Optimized energy efficiency (O2 trim, VFD control)
On-board system guides
Status indicators (no blinking lights or fault codes)
Plug-and-play replacement (configurable modular concept)
Easy data backup (USB flash drive, SD cards)
Compatible with flame rod and all existing Honeywell C70xx-series optical flame detectors by selection of correct Flame Amplifier Module.
Note: Each SLATETM system uses:
A multi voltage (24 VDC / 24..264 Vac) Base Module - R8001A1001, which mounts directly on the DIN rail.
Up to 12 SLATETM Modules can be connected to a single Base Module. An umbilical cable is available to divide the system over multiple DIN rails if needed.
Each of the plug-in modules uses its own a DIN rail mounting Sub Base - R8001S9001.

SLATE PC Software
Product description: SLATE AX PC software, based on Niagara AX 3.38 (Windows 7 or higher required)


ST7800A1005/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 2s.



ST7800A1013/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 7s.



ST7800A1021/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 10s.



ST7800A1039/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 30s.



ST7800A1047/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 40s.



ST7800A1054/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 60s.



ST7800A1062/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 90s.



ST7800A1070/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 2.5min.



ST7800A1088/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 4.0min.



ST7800A1096/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 6.0min.



ST7800A1104/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 9.0min.



ST7800A1112/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 12.0min.



ST7800A1120/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 15.0min.



ST7800A1138/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 22.0min.



ST7800A1146/U

Honeywell Burner Controls EC/RM7800-series
Purge timers

Prepurge time = 30.0min.



SV2-Vulcan-Spotlight

Honeywell Honeywell Thermal Solutions Product Catalogue

These pages show an overview and offer downloads of data sheets and certificates of the Honeywell branded Thermal Solutions products and solutions that are available for ordering through the Honeywell Europe sales channels, such as:
SLATETM burner/boiler management system
EC/RM7800-series "Blue Line" burner controllers
C7xxx-series optical flame sensors
IFM industrial flame monitoring products (former "IRIS Systems Inc.")
VE-series solenoid valves
C6097 gas pressure switches
and more...
Note: Kromschroeder is now part of Honeywell. An overview of and downloads for the Kromschroeder branded Thermal Solutions products can be found in Docuthek.
Please visit:: http://www.docuthek.com


Comment: Download SV2 brochure and promo video


Thermal-IQ-Spotlight

Honeywell Honeywell Thermal Solutions Product Catalogue

These pages show an overview and offer downloads of data sheets and certificates of the Honeywell branded Thermal Solutions products and solutions that are available for ordering through the Honeywell Europe sales channels, such as:
SLATETM burner/boiler management system
EC/RM7800-series "Blue Line" burner controllers
C7xxx-series optical flame sensors
IFM industrial flame monitoring products (former "IRIS Systems Inc.")
VE-series solenoid valves
C6097 gas pressure switches
and more...
Note: Kromschroeder is now part of Honeywell. An overview of and downloads for the Kromschroeder branded Thermal Solutions products can be found in Docuthek.
Please visit:: http://www.docuthek.com


Comment: Download Thermal IQ brochure and promo video


U2-1010S

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S cable connector models. For general use and Zone 2. Excluding cable, connector, PT adapter and air purge coupler.
Product description: Triple flame sensor.
Comment: 3G Ex nA nC T5
Flame detector: UVTron+UVSS+IR


U2-1010S-PF

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S models with factory mounted cable and 3/4" cable gland. For use in Zone 1. Excluding PT adapter and air purge coupler.
Product description: Triple sensor . Cable length 10 Ft (3 m).
Comment: Ex d IIC T6
Flame detector: UVTron+UVSS+IR


U2-1010S-PF-050

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S models with factory mounted cable and 3/4" cable gland. For use in Zone 1. Excluding PT adapter and air purge coupler.
Product description: Triple sensor. Cable length 50 Ft (15 m).
Comment: Ex d IIC T6
Flame detector: UVTron+UVSS+IR


U2-1010S-PF-100

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S models with factory mounted cable and 3/4" cable gland. For use in Zone 1. Excluding PT adapter and air purge coupler.
Product description: Triple sensor . Cable length 100 Ft (30 m).
Comment: Ex d IIC T6
Flame detector: UVTron+UVSS+IR


U2-1012S

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S cable connector models. For general use and Zone 2. Excluding cable, connector, PT adapter and air purge coupler.
Product description: Single flame sensor.
Comment: 3G Ex nA nC T5
Flame detector: IR


U2-1012S-PF

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S models with factory mounted cable and 3/4" cable gland. For use in Zone 1. Excluding PT adapter and air purge coupler.
Product description: Single sensor. Cable length 10 Ft (3 m).
Comment: Ex d IIC T6
Flame detector: IR


U2-1016S

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S cable connector models. For general use and Zone 2. Excluding cable, connector, PT adapter and air purge coupler.
Product description: Single flame sensor.
Comment: 3G Ex nA nC T5
Flame detector: UVTron


U2-1016S-PF

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S models with factory mounted cable and 3/4" cable gland. For use in Zone 1. Excluding PT adapter and air purge coupler.
Product description: Single sensor . Cable length 10 Ft (3 m).
Comment: Ex d IIC T6
Flame detector: UVTron


U2-1018S

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S cable connector models. For general use and Zone 2. Excluding cable, connector, PT adapter and air purge coupler.
Product description: Dual flame sensor.
Comment: 3G Ex nA nC T5
Flame detector: UVTron+IR


U2-1018S-PF

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head

The Honeywell U2-101xS series model all-in-one viewing head with integrated signal processor delivers flame discrimination in the toughest environments. With automatic setup and the ability to monitor UV and IR flame components simultaneously or separately, the U2-101xS all-in-one flame scanner offers improved burner up time and reliability.
Industrial process burners, multiple burner system.
Sensor: UV Tube (UVTron), UV photo diode (UVss), IR sensor or a combination of these three sensors
Response (peak): 210 nm (UVTron), 310 nm (UVss), 1400 nm (IR)
Technology: Flicker (UVss and IR), Pulse Count (UVTron)
100% immunity for X-Ray and Gamma radiation
Self-check (Electronic shutter): internal processor monitors tube health
All-in-one flame scanner: no additional wiring cabinet needed
Remote communication: Modbus RTU (2 wire RS485 compatible)
7 files for different configuration, that can be selected by applying or removing a voltage on the dedicated terminal (where FILE 0 is selected < 16Vdc and FILE X > 21Vdc) which this allows smooth file transition possible on mixed fuel burners. File 1..7 are selectable via the Modbus connection.
Touch screen user interface: A tempered and fully sealed glass touch wheel sensor: no mechanical moving buttons.
Local display: LED display for flame signal monitoring onsite
Configuration menu is locked to avoid accidental access automatically after a few minutes of inactivity. To unlock, make 1 full 360 turn with the finger around the touch screen window.
Power supply: 24Vdc
Protection class: NEMA 4x, IP66
Zone 2 Class 1 Div 2 Group A, B, C and D
U2-101xS: II 3G Ex nA nC T5 Gc
U2-101xS-PF: II 2G Ex d IIC T6 Gb / 2D Ex d tb IIIC T85 Db
Ambient temperature: -40...70C
Maximum humidity: 85%rh
Approvals: CE (EN298) for continuous operation (Europe).
CSA and FM (US)
IECEx and ATEX (explosion proof)
NCC/Inmetro (Brazil)
EAC (Russia)
KTL (Korea)
SIL 3 Capable
Housing (HxWxD): 117mm|117mm|155mm
Weight: 2.8kg
Output signal: 4-20 mA (or 0-20 mA) with scale multiplier for remote meter or DCS and local display.
Relay outputs: Wire flame and self-check relay contacts in serial to obtain fail-safe operation.
Flame relay: SPST - Normally Open
Self-check relay: SPST - Normally Open
End switch function/capacity: 30 Vdc, 1 A (resistive)
Note: For "PF" models it is highly recommended to use a pipe coupler (see R-518-xx accessories), for easy mounting on to a viewing pipe.
Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)
Control model: Flame switch
Outputs: 2xSPST
Flame failure response time: 1/2/3s selectable

U2-S models with factory mounted cable and 3/4" cable gland. For use in Zone 1. Excluding PT adapter and air purge coupler.
Product description: Dual sensor. Cable length 10 Ft (3 m).
Comment: Ex d IIC T6
Flame detector: UVTron+IR


UVSOURCE

Honeywell Industrial flame monitoring - U2-101xS All-In-One Viewing head
Parts and accessories - various parts

Ultra violet light source for UV sensor testing.



V4055A1031/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
Low pressure (200mbar) fluid power actuators

Fluid power actuators for Class "A" Safety Shutoff Gas Valves VE5000-series. Voltage: 120V, 50/60Hz.



V4055A1098/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
Low pressure (200mbar) fluid power actuators

Fluid power actuators for Class "A" Safety Shutoff Gas Valves VE5000-series. Voltage: 120V, 50/60Hz. With damper arm shaft.



V4055A1114/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
Low pressure (200mbar) fluid power actuators

Fluid power actuators for Class "A" Safety Shutoff Gas Valves VE5000-series. Voltage: 230V, 50/60Hz. With damper arm shaft.



V4055A1130/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
Low pressure (200mbar) fluid power actuators

Fluid power actuators for Class "A" Safety Shutoff Gas Valves VE5000-series. Voltage: 230V, 50/60Hz.



V4055A1239/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
Low pressure (200mbar) fluid power actuators

Fluid power actuators for Class "A" Safety Shutoff Gas Valves VE5000-series. Voltage: 230V, 50/60Hz.



V4055B1039/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
High pressure (360mbar) fluid power actuators

Fluid power actuators for Class "A" Safety Shutoff Gas Valves VE5000-series. Voltage: 120V, 50/60Hz. With damper arm shaft.



V4055B1088/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
High pressure (360mbar) fluid power actuators

Fluid power actuators for Class "A" Safety Shutoff Gas Valves VE5000-series. Voltage: 230V, 50/60Hz.



V4055B1096/U

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055
High pressure (360mbar) fluid power actuators

Fluid power actuators for Class "A" Safety Shutoff Gas Valves VE5000-series. Voltage: 230V, 50/60Hz.



V4295A1015

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 140mbar


V4295A1023

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 140mbar


V4295A1031

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 140mbar


V4295A1049

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 140mbar


V4295A1056

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 140mbar


V4295A1064

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 140mbar


V4295A1072

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 2 1/2
Max. operating pressure: 140mbar


V4295A1080

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 3
Max. operating pressure: 140mbar


V4295A1098

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 3/8
Max. operating pressure: 350mbar


V4295A1106

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 350mbar


V4295A1114

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 350mbar


V4295A1122

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 350mbar


V4295A1130

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 350mbar


V4295A1148/U

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 350mbar


V4295A1155

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 350mbar


V4295S1005

Honeywell Safety shut-off gas valve, normally open for North American market V4295S1

Class "B" Safety Shutoff Gas Valve.
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally OPEN (vent), fast closing.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Max. operating pressure: 140mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 3/4


V4295S1013

Honeywell Safety shut-off gas valve, normally open for North American market V4295S1

Class "B" Safety Shutoff Gas Valve.
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally OPEN (vent), fast closing.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Max. operating pressure: 140mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1


V4295S1021

Honeywell Safety shut-off gas valve, normally open for North American market V4295S1

Class "B" Safety Shutoff Gas Valve.
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally OPEN (vent), fast closing.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Max. operating pressure: 140mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

120 Vac versions
Valve dimension: Rp 1 1/4


V8295A1016

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

24 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 140mbar


V8295A1024

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

24 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 140mbar


V8295A1032

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

24 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 140mbar


V8295A1040

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

24 Vac versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 140mbar


V8295A1057

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

24 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 140mbar


V8295A1065

Honeywell Safety shut-off gas valve, normally closed for North American market V4295A1

Class "B" Safety Shutoff Gas Valve
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

24 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 140mbar


V8295S1006

Honeywell Safety shut-off gas valve, normally open for North American market V4295S1

Class "B" Safety Shutoff Gas Valve.
for control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally OPEN (vent), fast closing.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CSA, AGA
Upstream and downstream taps 1/4" NPT
Pipe connection: Internal threads
Threads type: NPT
Max. operating pressure: 140mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -40...63C

24 Vac versions
Valve dimension: Rp 3/4


VB420B1005

Honeywell Combination valve "VQ-Modular' with or without side valves
Internal by-pass valve, fast opening and with flow rate adjuster. For mounting on either side of the valve body.

Voltage: 115Vac, 3/4", screw terminals



VB420B1013

Honeywell Combination valve "VQ-Modular' with or without side valves
Internal by-pass valve, fast opening and with flow rate adjuster. For mounting on either side of the valve body.

Voltage: 230Vac, 3/4", screw terminals



VB420B1021

Honeywell Combination valve "VQ-Modular' with or without side valves
Internal by-pass valve, fast opening and with flow rate adjuster. For mounting on either side of the valve body.

Voltage: 115Vac, 3/4", DIN plug



VB420B1039

Honeywell Combination valve "VQ-Modular' with or without side valves
Internal by-pass valve, fast opening and with flow rate adjuster. For mounting on either side of the valve body.

Voltage: 230Vac, 3/4", DIN plug



VB420C1006

Honeywell Combination valve "VQ-Modular' with or without side valves
Internal by-pass valve, with adjustable slow opening, step-open and flow rate adjuster. For mounting on either side of the valve body.

Voltage: 115Vac, 3/4", screw terminals



VB420C1014

Honeywell Combination valve "VQ-Modular' with or without side valves
Internal by-pass valve, with adjustable slow opening, step-open and flow rate adjuster. For mounting on either side of the valve body.

Voltage: 230Vac, 3/4", screw terminals



VB420C1022

Honeywell Combination valve "VQ-Modular' with or without side valves
Internal by-pass valve, with adjustable slow opening, step-open and flow rate adjuster. For mounting on either side of the valve body.

Voltage: 115Vac, 3/4", DIN plug



VB420C1030

Honeywell Combination valve "VQ-Modular' with or without side valves
Internal by-pass valve, with adjustable slow opening, step-open and flow rate adjuster. For mounting on either side of the valve body.

Voltage: 230Vac, 3/4", DIN plug



VE4010A1006

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3/8
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Replacement coil: BB052301
Comments: no


VE4010B1054

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 3/8
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Comments: no


VE4010B1062

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3/8
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Comments: no


VE4010NB1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with flow restrictor
Valve dimension: Rp 3/8
Max. operating pressure: 200mbar


VE4010NB1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with flow restrictor
Valve dimension: Rp 3/8
Max. operating pressure: 200mbar


VE4010NC1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with openings curve
Valve dimension: Rp 3/8
Max. operating pressure: 200mbar


VE4015A1005

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Replacement coil: BB052301
Comments: no


VE4015A1013

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Replacement coil: BB051102DIN
Comments: no


VE4015A1070

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Replacement coil: BB052302
Comments: no


VE4015A1138

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Replacement coil: BB051102DIN
Comments: no


VE4015B1004

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Replacement coil: BB152301
Comments: no


VE4015B1012

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Replacement coil: BB151101
Comments: no


VE4015B1087

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Replacement coil: BB152305
Comments: no


VE4015B1095

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Replacement coil: BB151107
Comments: no


VE4015C1003

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Replacement coil: BB152301


VE4015C1110

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Replacement coil: BB152305


VE4015C1128

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Replacement coil: BB151107DIN


VE4015NB1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with flow restrictor
Valve dimension: Rp 1/2
Max. operating pressure: 200mbar


VE4015NB1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with flow restrictor
Valve dimension: Rp 1/2
Max. operating pressure: 200mbar


VE4015NC1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with openings curve
Valve dimension: Rp 1/2
Max. operating pressure: 200mbar


VE4015NC1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with openings curve
Valve dimension: Rp 1/2
Max. operating pressure: 200mbar


VE4020A1005

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB052325
Comments: no


VE4020A1054

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB051125
Comments: no


VE4020B1004

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB152325
Comments: no


VE4020B1046

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB152325
Comments: no


VE4020B1129

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB151125
Comments: no


VE4020B1137

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Replacement coil: BB152324
Comments: no


VE4020C1003

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB152325


VE4020C1060

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: DIN plug
Optional CPI-switch: MS052501


VE4020C1086

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Replacement coil: BB152324


VE4020NB1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with flow restrictor
Valve dimension: Rp 3/4
Max. operating pressure: 200mbar
Optional CPI-switch: MS052501


VE4020NB1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with flow restrictor
Valve dimension: Rp 3/4
Max. operating pressure: 200mbar
Optional CPI-switch: MS052501


VE4020NC1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with openings curve
Valve dimension: Rp 3/4
Max. operating pressure: 200mbar
Optional CPI-switch: MS052501


VE4020NC1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with openings curve
Valve dimension: Rp 3/4
Max. operating pressure: 200mbar
Optional CPI-switch: MS052501


VE4020S1038

Honeywell Solenoid gas valve, normally open VE4000S

Solenoid Gas Valve normally open.
The VE4000S1 and VE4000S2 series gas valves are safety relief solenoid valves used as vent valves in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally open
Media: natural gas, propane, air
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The VE4000S1 series are without Closed Position Indication (CPI) Switch, which can be ordered and installed separately.
The VE4000S2 series have the CPI switch factory installed.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

VE4000S1 Series (220...240Vac)
Valve dimension: Rp 3/4
Optional CPI-switch: MS052501
Replacement coil: BB152302


VE4020S1046

Honeywell Solenoid gas valve, normally open VE4000S

Solenoid Gas Valve normally open.
The VE4000S1 and VE4000S2 series gas valves are safety relief solenoid valves used as vent valves in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally open
Media: natural gas, propane, air
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The VE4000S1 series are without Closed Position Indication (CPI) Switch, which can be ordered and installed separately.
The VE4000S2 series have the CPI switch factory installed.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

VE4000S1 Series (110Vac)
Valve dimension: Rp 3/4
Optional CPI-switch: MS052501
Replacement coil: BB151101


VE4020S2044

Honeywell Solenoid gas valve, normally open VE4000S

Solenoid Gas Valve normally open.
The VE4000S1 and VE4000S2 series gas valves are safety relief solenoid valves used as vent valves in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally open
Media: natural gas, propane, air
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The VE4000S1 series are without Closed Position Indication (CPI) Switch, which can be ordered and installed separately.
The VE4000S2 series have the CPI switch factory installed.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

VE4000S2 Series with factory installed CPI switch (220...240Vac)
Valve dimension: Rp 3/4
Optional CPI-switch: included
Replacement coil: BB152302


VE4025A1004

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB052325
Comments: no


VE4025A1053

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB051125
Comments: no


VE4025A1145

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Replacement coil: BB052326DIN
Comments: no


VE4025A1194

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Replacement coil: BB051126DIN
Comments: no


VE4025B1003

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB152325
Comments: no


VE4025B1045

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB152325
Comments: no


VE4025B1078

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB151125
Comments: no


VE4025B1102

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Replacement coil: BB152325
Comments: no


VE4025B1110

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Replacement coil: BB151125
Comments: Viton


VE4025B1128

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Replacement coil: BB151125
Comments: no


VE4025C1002

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS052501
Replacement coil: BB152325


VE4025C1085

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: DIN plug
Optional CPI-switch: MS052501


VE4025C1119

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Replacement coil: BB152324


VE4025C1127

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501


VE4025NB1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with flow restrictor
Valve dimension: Rp 1
Max. operating pressure: 200mbar
Optional CPI-switch: MS052501


VE4025NB1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with flow restrictor
Valve dimension: Rp 1
Max. operating pressure: 200mbar
Optional CPI-switch: MS052501


VE4025NC1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with openings curve
Valve dimension: Rp 1
Max. operating pressure: 200mbar
Optional CPI-switch: MS052501


VE4025NC1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with openings curve
Valve dimension: Rp 1
Max. operating pressure: 200mbar
Optional CPI-switch: MS052501


VE4025S1037

Honeywell Solenoid gas valve, normally open VE4000S

Solenoid Gas Valve normally open.
The VE4000S1 and VE4000S2 series gas valves are safety relief solenoid valves used as vent valves in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally open
Media: natural gas, propane, air
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The VE4000S1 series are without Closed Position Indication (CPI) Switch, which can be ordered and installed separately.
The VE4000S2 series have the CPI switch factory installed.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

VE4000S1 Series (220...240Vac)
Valve dimension: Rp 1
Optional CPI-switch: MS052501
Replacement coil: BB152302


VE4025S1045

Honeywell Solenoid gas valve, normally open VE4000S

Solenoid Gas Valve normally open.
The VE4000S1 and VE4000S2 series gas valves are safety relief solenoid valves used as vent valves in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally open
Media: natural gas, propane, air
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The VE4000S1 series are without Closed Position Indication (CPI) Switch, which can be ordered and installed separately.
The VE4000S2 series have the CPI switch factory installed.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

VE4000S1 Series (110Vac)
Valve dimension: Rp 1
Optional CPI-switch: MS052501
Replacement coil: BB151101


VE4025S2035

Honeywell Solenoid gas valve, normally open VE4000S

Solenoid Gas Valve normally open.
The VE4000S1 and VE4000S2 series gas valves are safety relief solenoid valves used as vent valves in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally open
Media: natural gas, propane, air
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The VE4000S1 series are without Closed Position Indication (CPI) Switch, which can be ordered and installed separately.
The VE4000S2 series have the CPI switch factory installed.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

VE4000S2 Series with factory installed CPI switch (220...240Vac)
Valve dimension: Rp 1
Optional CPI-switch: included
Replacement coil: BB152302


VE4032A1000

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS054001
Replacement coil: BB052340
Comments: no


VE4032A1109

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS054001
Replacement coil: BB052340
Comments: no


VE4032B1108

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Replacement coil: BB151104
Comments: no


VE4032B1116

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Comments: no


VE4032C1032

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS054001
Replacement coil: BB152340


VE4032C1065

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001


VE4032NB1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with flow restrictor
Valve dimension: Rp 1 1/4
Max. operating pressure: 200mbar
Optional CPI-switch: MS054001


VE4032NB1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with flow restrictor
Valve dimension: Rp 1 1/4
Max. operating pressure: 200mbar
Optional CPI-switch: MS054001


VE4032NC1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with openings curve
Valve dimension: Rp 1 1/4
Max. operating pressure: 200mbar
Optional CPI-switch: MS054001


VE4032NC1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with openings curve
Valve dimension: Rp 1 1/4
Max. operating pressure: 200mbar
Optional CPI-switch: MS054001


VE4040A1003

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS054001
Replacement coil: BB052340
Comments: no


VE4040A1052

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS054001
Comments: no


VE4040A1144

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS054001
Replacement coil: BB052340
Comments: Bypass


VE4040A1219

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Replacement coil: BB052306DIN
Comments: no


VE4040A1227

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Comments: no


VE4040B1002

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS054001
Replacement coil: BB152326
Comments: no


VE4040B1044

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS054001
Replacement coil: BB152340
Comments: no


VE4040B1119

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Comments: Viton


VE4040B1127

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Replacement coil: BB151104
Comments: no


VE4040B1135

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Comments: no


VE4040C1001

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS054001
Replacement coil: BB152326


VE4040C1167

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001


VE4040C1175

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Replacement coil: BB152342DIN


VE4040NB1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with flow restrictor
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Optional CPI-switch: MS054001


VE4040NB1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with flow restrictor
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Optional CPI-switch: MS054001


VE4040NC1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with openings curve
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Optional CPI-switch: MS054001


VE4040NC1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with openings curve
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Optional CPI-switch: MS054001


VE4050A1002

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS055001
Replacement coil: BB052303
Comments: no


VE4050A1051

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS055001
Replacement coil: BB051152DIN
Comments: no


VE4050A1127

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS055001
Replacement coil: BB052303
Comments: no


VE4050A1184

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS055001
Replacement coil: BB051154DIN
Comments: no


VE4050B1001

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS055001
Replacement coil: BB152340
Comments: no


VE4050B1043

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS055001
Replacement coil: BB152303
Comments: no


VE4050B1118

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS055001
Replacement coil: BB152307
Comments: no


VE4050B1126

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS055001
Replacement coil: BB151153
Comments: no


VE4050C1000

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS055001
Replacement coil: BB152340


VE4050C1117

Honeywell Solenoid gas valve, normally closed, with characterized opening VE4000C1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment and characterized opening.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, slow opening, with maximum flow rate adjustment
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The maximum flow rate and the opening characteristics can be adjusted on top of the valve.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 30s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS055001
Replacement coil: BB152307DIN


VE4050NB1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with flow restrictor
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Optional CPI-switch: MS055001


VE4050NB1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with flow restrictor
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Optional CPI-switch: MS055001


VE4050NC1100

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

100 Vac versions with openings curve
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Optional CPI-switch: MS055001


VE4050NC1200

Honeywell Solenoid gas valve, normally closed, for Japanese market

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment (B-models) or openings characteristic (C-models) for the Japanese market (100/200 Vac).
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

200 Vac versions with openings curve
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Optional CPI-switch: MS055001


VE4065A1000

Honeywell Solenoid gas valve, normally closed VE4000A1

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Some models have 4x pressure taps 1/4" (2x on each side), marked as "Bypass" in the selection table.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 2 1/2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS056501
Replacement coil: BB052365
Comments: no


VE4065A3022

Honeywell Solenoid gas valve, normally closed VE4000A3

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN65
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS058001
Replacement coil: BB052381DIN


VE4065A3030

Honeywell Solenoid gas valve, normally closed VE4000A3

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: DN65
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS058001
Replacement coil: BB051181DIN


VE4065B1017

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 2 1/2
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS058001
Replacement coil: BB152365
Comments: no


VE4065B3005

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN65
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS058001
Replacement coil: BB152365


VE4065B3039

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN65
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS058001
Replacement coil: BB152380


VE4065B3047

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: DN65
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS058001
Replacement coil: BB151180


VE4065B3153

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN65
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS058001


VE4065B3161

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: DN65
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS058001


VE4080A3021

Honeywell Solenoid gas valve, normally closed VE4000A3

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN80
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS058001
Replacement coil: BB052382DIN


VE4080A3039

Honeywell Solenoid gas valve, normally closed VE4000A3

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: DN80
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS058001
Replacement coil: BB051105DIN


VE4080B1016

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: Rp 3
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS058001
Replacement coil: BB152380
Comments: no


VE4080B3004

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN80
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS058001
Replacement coil: BB152380


VE4080B3038

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN80
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS058001
Replacement coil: BB152382


VE4080B3046

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: DN80
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS058001


VE4080B3178

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN80
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS058001


VE408AA1007

Honeywell Solenoid gas valve, normally closed VE400AA

Class "A" AC powered, Safety Shutoff Solenoid Gas Valve.
For pilot and small burner applications in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: AC powered, non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: brass body for 1/4" version
Approvals: CE (EN161), AGA
Note: The VE410, VE415 and VE420 are replaced by the Kromschrder VGP series, respectively VGP 10, VGP 15 and VGP 20. For detailed specifications, please visit Docuthek.
Please visit:: http://www.docuthek.com
Valve dimension: Rp 1/4
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 500mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP65
Electrical connection: DIN plug

220..240 Vac versions
Rated voltage: 230Vac


VE408AA1015

Honeywell Solenoid gas valve, normally closed VE400AA

Class "A" AC powered, Safety Shutoff Solenoid Gas Valve.
For pilot and small burner applications in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: AC powered, non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: brass body for 1/4" version
Approvals: CE (EN161), AGA
Note: The VE410, VE415 and VE420 are replaced by the Kromschrder VGP series, respectively VGP 10, VGP 15 and VGP 20. For detailed specifications, please visit Docuthek.
Please visit:: http://www.docuthek.com
Valve dimension: Rp 1/4
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 500mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP65
Electrical connection: DIN plug

110..120 Vac versions
Rated voltage: 115Vac


VE408AA1049

Honeywell Solenoid gas valve, normally closed VE400AA

Class "A" AC powered, Safety Shutoff Solenoid Gas Valve.
For pilot and small burner applications in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: AC powered, non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: brass body for 1/4" version
Approvals: CE (EN161), AGA
Note: The VE410, VE415 and VE420 are replaced by the Kromschrder VGP series, respectively VGP 10, VGP 15 and VGP 20. For detailed specifications, please visit Docuthek.
Please visit:: http://www.docuthek.com
Valve dimension: Rp 1/4
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 500mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP65
Electrical connection: DIN plug

220..240 Vrac versions (needs DIN plug with integrated rectifier)
Rated voltage: 230Vrac


VE4100A3001

Honeywell Solenoid gas valve, normally closed VE4000A3

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN100
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS051001
Replacement coil: BB152300


VE4100A3068

Honeywell Solenoid gas valve, normally closed VE4000A3

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN100
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS051001


VE4100A3076

Honeywell Solenoid gas valve, normally closed VE4000A3

Class "A" Safety Shutoff Solenoid Gas Valve.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

110 Vac versions
Valve dimension: DN100
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS051001


VE4100B3000

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN100
Max. operating pressure: 200mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS051001
Replacement coil: BB152300


VE4100B3034

Honeywell Solenoid gas valve, normally closed, flanged connections VE4000B3

Class "A" Safety Shutoff Solenoid Gas Valve with flanged connections.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening
Media: natural gas, propane, air. Special versions for biogas available upon request
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
Adjustable maximum flow rate on top of the coil.
4 auxiliary pressure taps with Rp 1/4" threaded connections, 2 on the inlet side, 2 on the outlet side.
Other voltages are also available.
Optional Closed Position Indication Switch (CPI switch ) is ordered separately.
Pipe connection: PN16 Flanges as per EN 1092-1
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

220...240 Vac versions
Valve dimension: DN100
Max. operating pressure: 360mbar
Protection class: IP54
Electrical connection: PG11
Optional CPI-switch: MS051001


VE5065A3005

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055

Class "A" Safety Shutoff Gas Valve, for fluid power actuator V4055A/B.
For control and regulation of gaseous fluids in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast
Approvals: CE (EN161), AGA
Maximum inlet pressure depends on actuator model:
VE4065/80: 360mB maximum with V4055A actuator
VE4100: 360mB maximum with V4055B actuator
Pipe connection: Flanges
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: NEMA 3 / IP44

Valve bodies
Valve dimension: DN65


VE5080A3004

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055

Class "A" Safety Shutoff Gas Valve, for fluid power actuator V4055A/B.
For control and regulation of gaseous fluids in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast
Approvals: CE (EN161), AGA
Maximum inlet pressure depends on actuator model:
VE4065/80: 360mB maximum with V4055A actuator
VE4100: 360mB maximum with V4055B actuator
Pipe connection: Flanges
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: NEMA 3 / IP44

Valve bodies
Valve dimension: DN80


VE5080A3012

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055

Class "A" Safety Shutoff Gas Valve, for fluid power actuator V4055A/B.
For control and regulation of gaseous fluids in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast
Approvals: CE (EN161), AGA
Maximum inlet pressure depends on actuator model:
VE4065/80: 360mB maximum with V4055A actuator
VE4100: 360mB maximum with V4055B actuator
Pipe connection: Flanges
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: NEMA 3 / IP44

Valve bodies with additional pressure taps on in- and outlet side
Valve dimension: DN80


VE5100A3000

Honeywell Safety shut-off gas valve, normally closed, with fluid power actuator V4055

Class "A" Safety Shutoff Gas Valve, for fluid power actuator V4055A/B.
For control and regulation of gaseous fluids in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast
Approvals: CE (EN161), AGA
Maximum inlet pressure depends on actuator model:
VE4065/80: 360mB maximum with V4055A actuator
VE4100: 360mB maximum with V4055B actuator
Pipe connection: Flanges
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: NEMA 3 / IP44

Valve bodies
Valve dimension: DN100


VE8015B1042

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24 Vac versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Comments: no


VE8015B1059

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24...28 Vdc versions
Valve dimension: Rp 1/2
Max. operating pressure: 360mbar
Protection class: IP65
Electrical connection: DIN plug
Comments: no


VE8020B1042

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24 Vac versions
Valve dimension: Rp 3/4
Max. operating pressure: 200mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Comments: no


VE8020B1059

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24...28 Vdc versions
Valve dimension: Rp 3/4
Max. operating pressure: 200mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Comments: no


VE8020S1000

Honeywell Solenoid gas valve, normally open VE4000S

Solenoid Gas Valve normally open.
The VE4000S1 and VE4000S2 series gas valves are safety relief solenoid valves used as vent valves in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally open
Media: natural gas, propane, air
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The VE4000S1 series are without Closed Position Indication (CPI) Switch, which can be ordered and installed separately.
The VE4000S2 series have the CPI switch factory installed.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

VE4000S1 Series (24..28VDC)
Valve dimension: Rp 3/4
Optional CPI-switch: MS052501


VE8025B1058

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24 Vac versions
Valve dimension: Rp 1
Max. operating pressure: 200mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Comments: no


VE8025B1066

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24...28 Vdc versions
Valve dimension: Rp 1
Max. operating pressure: 200mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS052501
Comments: no


VE8025S1009

Honeywell Solenoid gas valve, normally open VE4000S

Solenoid Gas Valve normally open.
The VE4000S1 and VE4000S2 series gas valves are safety relief solenoid valves used as vent valves in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally open
Media: natural gas, propane, air
Materials: aluminium die cast body
Approvals: CE (EN161), AGA
The VE4000S1 series are without Closed Position Indication (CPI) Switch, which can be ordered and installed separately.
The VE4000S2 series have the CPI switch factory installed.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Max. operating pressure: 360mbar
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C
Protection class: IP54
Electrical connection: PG11

VE4000S1 Series (24..28VDC)
Valve dimension: Rp 1
Optional CPI-switch: MS052501


VE8032B1039

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24...28 Vdc versions
Valve dimension: Rp 1 1/4
Max. operating pressure: 200mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Comments: no


VE8040B1032

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24 Vac versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Comments: no


VE8040B1040

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24...28 Vdc versions
Valve dimension: Rp 1 1/2
Max. operating pressure: 200mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS054001
Comments: no


VE8050B1023

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24 Vac versions
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS055001
Comments: no


VE8050B1031

Honeywell Solenoid gas valve, normally closed, with flow rate adjustment VE4000B1

Class "A" Safety Shutoff Solenoid Gas Valve, with maximum flow rate adjustment.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: non regulated ON/OFF normally closed, fast opening, with maximum flow rate adjustment.
Media: natural gas, propane, air. Special versions for biogas available upon request.
Materials: aluminium die cast body.
Approvals: CE (EN161), AGA
The maximum flow rate can be adjusted on top of the valve
Optional Closed Position Indication Switch (CPI switch ) can be ordered separately.
Pipe connection: Internal thread as per ISO 7/1 (Rp)
Threads type: BSP
Maximum opening time: 1s
Maximum closing time: 1s
Ambient temperature: -15...60C

24...28 Vdc versions
Valve dimension: Rp 2
Max. operating pressure: 200mbar
Protection class: IP65
Electrical connection: DIN plug
Optional CPI-switch: MS055001
Comments: no


VMUxxx

Honeywell Safety combination shutoff gas valve with integrated gas pressure regulation
Venturi mixing unit

Venturi mixing unit for premix applications in combination with VR4xxVx and VR8xxVx gas valve models only (1:1 gas/air)



VP420B1003

Honeywell Combination valve "VQ-Modular' with or without side valves
Pilot valve, fast opening and with flow rate adjuster. With Rp 3/4" internal pipe thread. For mounting on either side of the valve body.

Voltage: 115Vac, 3/4", screw terminals



VP420B1011

Honeywell Combination valve "VQ-Modular' with or without side valves
Pilot valve, fast opening and with flow rate adjuster. With Rp 3/4" internal pipe thread. For mounting on either side of the valve body.

Voltage: 230Vac, 3/4", screw terminals



VP420B1029

Honeywell Combination valve "VQ-Modular' with or without side valves
Pilot valve, fast opening and with flow rate adjuster. With Rp 3/4" internal pipe thread. For mounting on either side of the valve body.

Voltage: 115Vac, 3/4", DIN plug



VP420B1037

Honeywell Combination valve "VQ-Modular' with or without side valves
Pilot valve, fast opening and with flow rate adjuster. With Rp 3/4" internal pipe thread. For mounting on either side of the valve body.

Voltage: 230Vac, 3/4", DIN plug



VP420C1004

Honeywell Combination valve "VQ-Modular' with or without side valves
Pilot valve, with adjustable slow opening, step-open and flow rate adjuster. With Rp 3/4" internal pipe thread. For mounting on either side of the valve body.

Voltage: 115Vac, 3/4", screw terminals



VP420C1012

Honeywell Combination valve "VQ-Modular' with or without side valves
Pilot valve, with adjustable slow opening, step-open and flow rate adjuster. With Rp 3/4" internal pipe thread. For mounting on either side of the valve body.

Voltage: 230Vac, 3/4", screw terminals



VP420C1020

Honeywell Combination valve "VQ-Modular' with or without side valves
Pilot valve, with adjustable slow opening, step-open and flow rate adjuster. With Rp 3/4" internal pipe thread. For mounting on either side of the valve body.

Voltage: 115Vac, 3/4", DIN plug



VP420C1038

Honeywell Combination valve "VQ-Modular' with or without side valves
Pilot valve, with adjustable slow opening, step-open and flow rate adjuster. With Rp 3/4" internal pipe thread. For mounting on either side of the valve body.

Voltage: 230Vac, 3/4", DIN plug



VQ420MA1004

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 230 Vac
Valve size: 3/4inch
Maximum opening time: 1s
Electrical connection: PG11
Protection class: IP54
Power consumption: 15W
Maximum flow: 8m3/h
Optional CPI-switch: MS062001
Spare coil V1: BB052302PG
Spare coil V2: BB052302PG


VQ420MA1012

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 230 Vac
Valve size: 3/4inch
Maximum opening time: 1s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 15W
Maximum flow: 8m3/h
Optional CPI-switch: MS062001
Spare coil V1: BB052302DIN
Spare coil V2: BB052305DIN


VQ420MB1003

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve fast opening and with flow rate adjuster
Supply voltage: 230 Vac
Valve size: 3/4inch
Maximum opening time: 1s
Electrical connection: PG11
Protection class: IP54
Power consumption: 15W
Maximum flow: 8m3/h
Optional CPI-switch: MS062001
Spare coil V1: BB052302PG
Spare coil V2: BB152305PG


VQ420MC1002

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve adjustable slow opening, step-open and flow rate adjuster
Supply voltage: 230 Vac
Valve size: 3/4inch
Maximum opening time: 30s
Electrical connection: PG11
Protection class: IP54
Power consumption: 15W
Maximum flow: 8m3/h
Optional CPI-switch: MS062001
Spare coil V1: BB052302PG
Spare coil V2: no


VQ425MA1005

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 230 Vac
Valve size: 1inch
Maximum opening time: 1s
Electrical connection: PG11
Protection class: IP54
Power consumption: 21.1W
Maximum flow: 11m3/h
Optional CPI-switch: MS062501
Spare coil V1: BB052326PG
Spare coil V2: BB052326PG


VQ425MA1013

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 230 Vac
Valve size: 1inch
Maximum opening time: 1s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 21.1W
Maximum flow: 11m3/h
Optional CPI-switch: MS062501
Spare coil V1: BB052326DIN
Spare coil V2: BB052326DIN


VQ425MA1038

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 115 Vac
Valve size: 1inch
Maximum opening time: 1s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 23.9W
Maximum flow: 11m3/h
Optional CPI-switch: MS062501
Spare coil V1: BB051126DIN
Spare coil V2: BB051126DIN


VQ425MB1004

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve fast opening and with flow rate adjuster
Supply voltage: 230 Vac
Valve size: 1inch
Maximum opening time: 1s
Electrical connection: PG11
Protection class: IP54
Power consumption: 21.1W
Maximum flow: 11m3/h
Optional CPI-switch: MS062501
Spare coil V1: BB052326PG
Spare coil V2: BB152324PG


VQ425MB1012

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve fast opening and with flow rate adjuster
Supply voltage: 230 Vac
Valve size: 1inch
Maximum opening time: 1s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 21.1W
Maximum flow: 11m3/h
Optional CPI-switch: MS062501
Spare coil V1: BB052326DIN
Spare coil V2: BB152324DIN


VQ425MC1003

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve adjustable slow opening, step-open and flow rate adjuster
Supply voltage: 230 Vac
Valve size: 1inch
Maximum opening time: 30s
Electrical connection: PG11
Protection class: IP54
Power consumption: 21.1W
Maximum flow: 11m3/h
Optional CPI-switch: MS062501
Spare coil V1: BB052326PG
Spare coil V2: no


VQ425MC1011

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve adjustable slow opening, step-open and flow rate adjuster
Supply voltage: 230 Vac
Valve size: 1inch
Maximum opening time: 30s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 21.1W
Maximum flow: 11m3/h
Optional CPI-switch: MS062501
Spare coil V1: BB052326DIN
Spare coil V2: no


VQ440MA1006

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 230 Vac
Valve size: 1.1/2inch
Maximum opening time: 1s
Electrical connection: PG11
Protection class: IP54
Power consumption: 46.5W
Maximum flow: 31m3/h
Optional CPI-switch: MS064001
Spare coil V1: BB052306PG
Spare coil V2: BB052306PG


VQ440MA1014

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 230 Vac
Valve size: 1.1/2inch
Maximum opening time: 1s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 46.5W
Maximum flow: 31m3/h
Optional CPI-switch: MS064001
Spare coil V1: BB052306DIN
Spare coil V2: BB052306DIN


VQ440MA1030

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 115 Vac
Valve size: 1.1/2inch
Maximum opening time: 1s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 46.5W
Maximum flow: 31m3/h
Optional CPI-switch: MS064001
Spare coil V1: BB051152DIN
Spare coil V2: BB051152DIN


VQ440MA1048

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 230 Vac
Valve size: 1.1/2inch
Maximum opening time: 1s
General features: Viton
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 46.5W
Maximum flow: 31m3/h
Optional CPI-switch: MS064001
Spare coil V1: BB052306DIN
Spare coil V2: BB052306DIN


VQ440MB1005

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve fast opening and with flow rate adjuster
Supply voltage: 230 Vac
Valve size: 1.1/2inch
Maximum opening time: 1s
Electrical connection: PG11
Protection class: IP54
Power consumption: 46.5W
Maximum flow: 31m3/h
Optional CPI-switch: MS064001
Spare coil V1: BB052306PG
Spare coil V2: BB152342PG


VQ440MB1013

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve fast opening and with flow rate adjuster
Supply voltage: 230 Vac
Valve size: 1.1/2inch
Maximum opening time: 1s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 46.5W
Maximum flow: 31m3/h
Optional CPI-switch: MS064001
Spare coil V1: BB052306DIN
Spare coil V2: BB152342DIN


VQ440MC1004

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve adjustable slow opening, step-open and flow rate adjuster
Supply voltage: 230 Vac
Valve size: 1.1/2inch
Maximum opening time: 30s
Electrical connection: PG11
Protection class: IP54
Power consumption: 46.5W
Maximum flow: 31m3/h
Optional CPI-switch: MS064001
Spare coil V1: BB052306PG
Spare coil V2: no


VQ440MC1012

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve adjustable slow opening, step-open and flow rate adjuster
Supply voltage: 230 Vac
Valve size: 1.1/2inch
Maximum opening time: 30s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 46.5W
Maximum flow: 31m3/h
Optional CPI-switch: MS064001
Spare coil V1: BB052306DIN
Spare coil V2: no


VQ450BB1005M

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve adjustable slow opening, step-open and flow rate adjuster
Supply voltage: 230 Vac
Valve size: 2inch
Maximum opening time: 30s
General features: Factory mounted 1" by-pass valve
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 61W
Maximum flow: 40m3/h
Optional CPI-switch: MS065001
Spare coil V1: BB052309DIN
Spare coil V2: no


VQ450MA1007

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 230 Vac
Valve size: 2inch
Maximum opening time: 1s
Electrical connection: PG11
Protection class: IP54
Power consumption: 61W
Maximum flow: 40m3/h
Optional CPI-switch: MS065001
Spare coil V1: BB052309PG
Spare coil V2: BB052309PG


VQ450MA1015

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First and second valve fast opening
Supply voltage: 230 Vac
Valve size: 2inch
Maximum opening time: 1s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 61W
Maximum flow: 40m3/h
Optional CPI-switch: MS065001
Spare coil V1: BB052309DIN
Spare coil V2: BB052309DIN


VQ450MB1006

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve fast opening and with flow rate adjuster
Supply voltage: 230 Vac
Valve size: 2inch
Maximum opening time: 1s
Electrical connection: PG11
Protection class: IP54
Power consumption: 61W
Maximum flow: 40m3/h
Optional CPI-switch: MS065001
Spare coil V1: BB052309PG
Spare coil V2: BB152307PG


VQ450MB1014

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve fast opening and with flow rate adjuster
Supply voltage: 230 Vac
Valve size: 2inch
Maximum opening time: 1s
Electrical connection: DIN plug
Protection class: IP65
Power consumption: 61W
Maximum flow: 40m3/h
Optional CPI-switch: MS065001
Spare coil V1: BB052309DIN
Spare coil V2: BB152307DIN


VQ450MC1005

Honeywell Combination valve "VQ-Modular' with or without side valves

Class "A" Combination Gas Valve, up to 2" connection size. Special flanges are available for pipe sizes from 1/2" up to 2". Modular design:
other valves can be fitted to each side of the valve body, such as a vent valve, pilot valve or or external bypass valve;
special gas pressure switch models are available for direct mounting on either side of the valve body.
For control and regulation of gaseous fuels in gas power burners, gas boilers, ovens, furnaces and other gas consuming appliances.
Gas valve type: 2 safety shutoff valves in series, without pressure regulator.
First safety valve V1: Always fast opening.
Second safety valve V2: Available models:
MA - fast open
MB - fast open with flow rate adjuster (factory set at fully open)
MC - adjustable slow open (1..30 sec) with flow rate adjuster and step-open feature (factory settings: no step, ca. 6 sec slow-open and maximum flow)
Port connection: Honeywell flanges
Media: Designed for use with natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Closing spring: AISI 302 steel.
Valve plunger: Chrome plated Fe 360B steel sliding on anti-friction bearing.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE (EN161), AGA
The valve solenoids are suitable for permanent energizing, such as applications in continuous operation.
Various pressure tap points are available on both sides of the valve body as well as on the flanges.
An optional Closed Position Indication Switch (CPI) can be mounted on the bottom of the first safety valve V1
Note: The VQ-Modular is designed for a maximum operating frequency of one cycle per minute.
The small body size models are designed for ca. 500k cycles of operation.
The large body size models are designed for ca. 300k cycles of operation.
IMPORTANT: the VQ-Modular does not have an integrated screen at the inlet. For the inlet side always use flange models KTCOMSxx and for the outlet side flange models KTCOMBxx. KTCOMSxx can also be ordered for use at the outlet side, but then the included screen must be removed.
Max. operating pressure: 360mbar
Ambient temperature: -15...60C
Maximum closing time: 1s

First valve fast opening. Second valve adjustable slow opening, step-open and flow rate adjuster
Supply voltage: 230 Vac
Valve size: 2inch
Maximum opening time: 30s
Electrical connection: PG11
Protection class: IP54
Power consumption: 61W
Maximum flow: 40m3/h
Optional CPI-switch: MS065001
Spare coil V1: BB052309PG
Spare coil V2: no


VR4xx-series

Honeywell Safety combination shutoff gas valve with integrated gas pressure regulation

The VR400 / V4730 Series servo regulated combination valves are used for control and regulation of gaseous fuels in gas fired power burners, atmospheric gas boilers, melting furnaces, incinerators and other gas consuming appliances. These servo regulated combination valves are available in the following different versions:
VRB15 (pipe sizes 1/2)
VRB20 (pipe sizes 3/4)
VRB25 (pipe sizes 1)
VR415/VR815 (pipe sizes 1/2)
VR420/VR820 (pipe sizes 3/4")
VR425/VR825 (pipe sizes 1)
VR432/VR832 (pipe sizes 1-1/4)
VR434/VR834 (pipe sizes 1-1/4)
Designed for but not limited to commercial burner and boiler applications
Port connection: flanges
Media: Natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE, AGA


Supply voltage: 220..240 Vac


VR8xx-series

Honeywell Safety combination shutoff gas valve with integrated gas pressure regulation

The VR400 / V4730 Series servo regulated combination valves are used for control and regulation of gaseous fuels in gas fired power burners, atmospheric gas boilers, melting furnaces, incinerators and other gas consuming appliances. These servo regulated combination valves are available in the following different versions:
VRB15 (pipe sizes 1/2)
VRB20 (pipe sizes 3/4)
VRB25 (pipe sizes 1)
VR415/VR815 (pipe sizes 1/2)
VR420/VR820 (pipe sizes 3/4")
VR425/VR825 (pipe sizes 1)
VR432/VR832 (pipe sizes 1-1/4)
VR434/VR834 (pipe sizes 1-1/4)
Designed for but not limited to commercial burner and boiler applications
Port connection: flanges
Media: Natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE, AGA


Supply voltage: 24 Vac


VRBxx-series

Honeywell Safety combination shutoff gas valve with integrated gas pressure regulation

The VR400 / V4730 Series servo regulated combination valves are used for control and regulation of gaseous fuels in gas fired power burners, atmospheric gas boilers, melting furnaces, incinerators and other gas consuming appliances. These servo regulated combination valves are available in the following different versions:
VRB15 (pipe sizes 1/2)
VRB20 (pipe sizes 3/4)
VRB25 (pipe sizes 1)
VR415/VR815 (pipe sizes 1/2)
VR420/VR820 (pipe sizes 3/4")
VR425/VR825 (pipe sizes 1)
VR432/VR832 (pipe sizes 1-1/4)
VR434/VR834 (pipe sizes 1-1/4)
Designed for but not limited to commercial burner and boiler applications
Port connection: flanges
Media: Natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE, AGA


Supply voltage: 220..240 Vac


VV420A1002

Honeywell Combination valve "VQ-Modular' with or without side valves
Normally open vent valve series. With Rp 3/4" internal pipe thread, for mounting on the right side of the valve body.

Voltage: 115Vac, 3/4", screw terminals



VV420A1010

Honeywell Combination valve "VQ-Modular' with or without side valves
Normally open vent valve series. With Rp 3/4" internal pipe thread, for mounting on the right side of the valve body.

Voltage: 230Vac, 3/4", screw terminals



VV420A1028

Honeywell Combination valve "VQ-Modular' with or without side valves
Normally open vent valve series. With Rp 3/4" internal pipe thread, for mounting on the right side of the valve body.

Voltage: 115Vac, 3/4", DIN plug



VV420A1036

Honeywell Combination valve "VQ-Modular' with or without side valves
Normally open vent valve series. With Rp 3/4" internal pipe thread, for mounting on the right side of the valve body.

Voltage: 230Vac, 3/4", DIN plug



VV420A1044

Honeywell Combination valve "VQ-Modular' with or without side valves
Normally open vent valve series. With Rp 3/4" internal pipe thread, for mounting on the left side of the valve body.

Voltage: 115Vac, 3/4", screw terminals



VV420A1051

Honeywell Combination valve "VQ-Modular' with or without side valves
Normally open vent valve series. With Rp 3/4" internal pipe thread, for mounting on the left side of the valve body.

Voltage: 230Vac, 3/4", screw terminals



VV420A1069

Honeywell Combination valve "VQ-Modular' with or without side valves
Normally open vent valve series. With Rp 3/4" internal pipe thread, for mounting on the left side of the valve body.

Voltage: 115Vac, 3/4", DIN plug



VV420A1077

Honeywell Combination valve "VQ-Modular' with or without side valves
Normally open vent valve series. With Rp 3/4" internal pipe thread, for mounting on the left side of the valve body.

Voltage: 230Vac, 3/4", DIN plug



Video

Honeywell Intelligent safety combination shutoff gas valve with integrated smart technology

The "Vulcan" SV2 Series servo regulated combination valves are used for control and regulation of gaseous fuels in gas fired power burners, atmospheric gas boilers, melting furnaces, incinerators and other gas consuming appliances. These smart combination valves are available in various configurations from 3/4" up to 3". the following different versions:
Designed for but not limited to commercial burner and boiler applications
Gas valve type: Class A safety shut-off valves
Port connection: flanges
Media: Natural gas, butane or propane.
Materials: Valve body: aluminium die cast body.
Seals and gaskets: Hydrocarbon resistant NBR rubber type.
Approvals: CE, UL, CSA
Note: Contact a Honeywell Thermal Solutions Representative for more information.
Supply voltage: 24/120/230 Vac

Downloads
Comment: Promo Video


WATCHDOGIIIBE

Honeywell Flare monitoring system

Watchdog III is a flare stack monitoring system, guarding against the venting of hazardous gases in the atmosphere.
Can be used for continuous onsite flare monitoring
The fail-safe and well proven UVtron technology is used for flame detection.
Totally immune to sunlight:
Can be installed anywhere in a 360 degree radius around the flare stack. Operates in the 210 nm range of the spectrum (UV)
The viewing head can be mounted outside a explosion hazardous location:
The WATCHDOG viewing head can detect a flare more than 300 m away.
The signal processing unit can be mounted inside a nearby wiring cabinet.
Temperature range: -40...80C
Bus system description: Serial communication: RS422/485 (differential
4800, 9600, 19200 or 38400 baud (selectable)
Hardware outputs: Early indication: 2 x SPDT
Delayed indication: 1 x SPDT
0..20 mA or 4..20 mA (selectable)
Note: Because Honeywell cable accessories are of USA origin, all cable lengths are measured in Ft (Feet, 1 Ft = 304.8mm)

Complete set
Product description: Complete set, consists of P222, S256BE and ASYS5XXBE cable/connector assembly (15 m - 50 Ft).
Supply voltage: 85..264 Vac